EZC250H44250 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC250H44250 — Electrical
ParameterValue
Network type (AC/DC)AC DC
Rated current [In]250 A at 40 °C
Rated operational voltage [Ue]550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P
EZC250H44250 — Protection & Performance
ParameterValue
Breaking capacity10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 125 V DC 1P conforming to IEC 60947-2 30 kA Icu at 250 V DC 2P conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 125 V DC conforming to IEC 60947-2 15 kA at 250 V DC conforming to IEC 60947-2 12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating250 A at 50 °C
Trip unit nameTM-D
Protection typeOverload protection Short-circuit protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Local signallingPositive contact indication
EZC250H44250 — Mechanical
ParameterValue
Connection pitch35 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC250H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width140 mm
Height165 mm
Depth60 mm
EZC250H44250 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC250H44250 — Approvals
ParameterValue
StandardsJIS C8201-2-2 GB/T 14048.2 EN/IEC 60947-1 EN/IEC 60947-2

Product details

The EZC250H44250 is a 4-pole thermal-magnetic circuit breaker from the EasyPact EZC250H series, rated 250 A at 40 °C ambient (250 A at 50 °C with the TM-D trip unit). That 250 A continuous rating sets the maximum load current it can carry without tripping — sized for a main feeder or large distribution subfeed in a panel. The H breaking capacity code means it delivers 85 kA Icu at 220–240 V AC and 36 kA at 380–415 V AC, so it can interrupt high fault currents typical of transformer-fed industrial distribution without upstream fuses taking over. At 550 V AC it still holds 10 kA Icu, covering 480 V class systems with headroom. The thermal-magnetic TM-D trip unit provides overload protection (thermal bimetal) and short-circuit protection (magnetic solenoid) in one package — no separate relay or CT needed. Category A utilization means it is not intended for cascaded selectivity with intentional short-time delay; coordination with downstream breakers relies on the instantaneous magnetic trip curve. Suitability for isolation (IEC 60947-2) confirms it can be used as a visible-break disconnector for safe maintenance.

Deployment context

Fixed backplate mount with front connections — the breaker bolts to a panel backplate, and cables land on the front terminals. The 35 mm connection pitch matches standard busbar or cable-lug spacing. Pollution degree 3 (IEC 60947) means it is rated for conductive dust or occasional condensation inside the enclosure — typical of industrial switchrooms.

MPN