Schneider Electric EZC250N44100 — Circuit Breaker Accessories

EZC250N44100 EasyPact EZC250N Circuit Breaker, 100 A, 4P, TM

MPNEZC250N44100
Obsolete

Schneider Electric EasyPact EZC250N, 4-pole circuit breaker, TM-D thermal-magnetic trip unit, 100 A at 40 °C, 20 kA Icu at 440 V AC, toggle control, front connection, fixed backplate mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

EZC250N44100 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC250N44100 — Electrical
ParameterValue
Network type (AC/DC)DC AC
Rated current [In]100 A at 40 °C
Rated operational voltage [Ue]550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P
EZC250N44100 — Protection & Performance
ParameterValue
Breaking capacity20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 125 V DC 1P conforming to IEC 60947-2 20 kA Icu at 250 V DC 2P conforming to IEC 60947-2 8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 125 V DC conforming to IEC 60947-2 10 kA at 250 V DC conforming to IEC 60947-2 4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN
Trip unit technologyThermal-magnetic
Trip unit rating100 A at 50 °C
Trip unit nameTM-D
Protection typeOverload protection Short-circuit protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Local signallingPositive contact indication
EZC250N44100 — Mechanical
ParameterValue
Connection pitch35 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC250N
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width140 mm
Height165 mm
Depth60 mm
EZC250N44100 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC250N44100 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 JIS C8201-2-2 GB/T 14048.2 EN/IEC 60947-2

Product details

The EZC250N44100 is a 4-pole EasyPact EZC250N moulded-case circuit breaker from Schneider Electric, fitted with a TM-D thermal-magnetic trip unit rated 100 A at 40 °C (100 A at 50 °C). It is a distribution-class breaker (Category A per IEC 60947-2) with a fixed backplate mount and front-facing connections — designed for panel builders who need a compact, no-frills main or feeder breaker in a 4P footprint. Rated operational voltage goes to 550 V AC 50/60 Hz and 250 V DC; insulation voltage is 690 V AC. The breaking capacity code N delivers 20 kA Icu at 440 V AC, 25 kA at 380–415 V AC, and 50 kA at 220–240 V AC — enough for most commercial and light industrial distribution boards. At 125 V DC single-pole it still holds 20 kA Icu. That keeps the BOM simple but means the 100 A rating is the only setting; if the load draw changes, the breaker itself must be swapped.

Mounts fixed to a backplate via the four screw holes — no DIN-rail clip, so plan for a dedicated mounting footprint. Dimensions are 165 mm high, 140 mm wide, 60 mm deep, with a 35 mm connection pitch on the front terminals. IP20 finger-safe protection on the front, IK07 impact resistance. The toggle handle gives positive contact indication (ON/OFF/TRIPPED) visible through the enclosure window.

Designed and tested to EN/IEC 60947-1 and -2, JIS C8201-2-2, and GB/T 14048.2. Mechanical durability is 10,000 cycles.

Frequently asked questions

Where can I buy EZC250N44100 and how do I get a price?

The EZC250N44100 is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm availability and current pricing.

What is the closest pin-compatible alternative to EZC250N44100 in this component family?

Within the EasyPact EZC250N family, the closest alternative is the same frame with a different trip rating or with an electronic trip unit (EZC250H or EZC250F series). Pin-compatibility depends on the mounting footprint and connection pitch — the 35 mm pitch and backplate mount are shared across the EZC250N range, so swapping to a different current rating within the same frame is a direct mechanical fit.

What compliance documentation does this brand provide for EZC250N44100 (RoHS, REACH, UL, IEC)?

The EZC250N44100 is certified to EN/IEC 60947-1 and -2, JIS C8201-2-2, and GB/T 14048.2. It carries a CE marking for the European market. RoHS and REACH compliance documentation is typically available from Schneider Electric upon request — the product is designed for global distribution and meets the applicable environmental directives.

MPN
EZC250N44100