Specifications

EZC400H3350 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC400H3350 — Electrical
ParameterValue
Network type (AC/DC)AC
Rated current [In]400 A at 40 °C
Rated operational voltage [Ue]440 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]8 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description3P
EZC400H3350 — Protection & Performance
ParameterValue
Breaking capacity50 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]25 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating350 A at 50 °C
Trip unit nameTM-D
Protection typeOverload protection Short-circuit protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Electrical durabilityCategory A: 4000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
Local signallingPositive contact indication
Contact position indicatorYes
EZC400H3350 — Mechanical
ParameterValue
Connection pitch44 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC400H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width140 mm
Height255 mm
Depth140 mm
ColourBlack
EZC400H3350 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC400H3350 — Approvals
ParameterValue
StandardsGB/T 14048.2 EN/IEC 60947-1 EN/IEC 60947-2 JIS C8201-2-2

Product details

The Schneider Electric EZC400H3350 is a 3-pole EasyPact EZC400H molded case circuit breaker rated 400 A at 40 °C (In) with a TM-D thermal-magnetic trip unit. The TM-D trip unit provides both overload (thermal) and short-circuit (magnetic) protection in one package, with a magnetic trip threshold of 3200 A. Mounts fixed to a backplate (not DIN rail), so plan for a dedicated mounting surface in the enclosure. Front-connect terminals on both line and load sides simplify bus-bar or cable routing in a standard distribution panel layout.

Compliance documentation is available: the breaker carries IEC 60947-2, GB/T 14048.2, and JIS C8201-2-2 approvals, plus IP20 and IK07 mechanical impact protection.

Integration notes

Dimensions: 255 mm high, 140 mm wide, 140 mm deep. The 44 mm pole pitch matches standard bus-bar spacing for 3-pole breakers in this class. Mechanical durability is 10,000 cycles; electrical durability is 4,000 cycles at 415 V AC. That's typical for a distribution breaker — not intended for frequent switching duty like a contactor, but fine for isolation and backup protection in a fixed installation.

Frequently asked questions

What are the key ratings for EZC400H3350?

Rated current 400 A at 40 °C, breaking capacity 50 kA Icu at 400...415 V AC, 3-pole, TM-D thermal-magnetic trip unit with magnetic trip at 3200 A. Suitability for isolation is confirmed per IEC 60947-2.

Where can I buy EZC400H3350?

This part is sourced to order against an RFQ through our independent distribution network. Submit a request for current pricing and availability — we confirm both at quote time.

What compliance documentation does EZC400H3350 carry?

It is certified to IEC 60947-2, GB/T 14048.2, and JIS C8201-2-2. IP20 finger protection and IK07 impact resistance are standard. The breaker is suitable for isolation per IEC 60947-2.