If your enclosure runs hotter, the TM-D thermal-magnetic trip unit will derate; the trip unit itself is rated 300 A at 50 °C, so that's your ceiling in a warm cabinet. For a 400 A distribution breaker feeding a downstream panel, that 36 kA gives you solid selectivity headroom against most transformer secondary faults. The Utilisation category is A, meaning it's not intended for frequent switching of motor loads — this is a distribution breaker, not a motor circuit protector.
Fixed mount on a backplate, front connection both top and bottom. IP20 finger-safe protection means it's suitable for enclosed distribution boards — no shock hazard during maintenance with the door open. IK07 impact resistance handles accidental tool drops during commissioning. Complies with EN/IEC 60947-2 and 60947-1, plus GB/T 14048.2 and JIS C8201-2-2 for Chinese and Japanese markets.