Schneider Electric GV2DP104F7 — Miniature Circuit Breakers (MCB)

Schneider GV2DP104F7 TeSys Deca DOL Starter, 0.4-0.63A, Obso

MPNGV2DP104F7
Obsolete

Schneider Electric TeSys Deca GV2DP104F7 DOL combination starter, 0.4 to 0.63 A thermal adjustment, 110 VAC 50/60 Hz coil, 130 kA breaking capacity at 400/415 V, obsolete.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2DP104F7 — Identification
ParameterValue
Product range (series)TeSys Deca
Product/component typeMotor starter
GV2DP104F7 — Ratings
ParameterValue
Poles configuration3P
Utilisation categoryAC-3
GV2DP104F7 — Mechanical
ParameterValue
Width45 mm
Height176.4 mm
Depth105.6 mm
GV2DP104F7 — Other specifications
ParameterValue
Motor power0.12 kW at 400/415 V AC 50/60 Hz 0.18 kW at 400/415 V AC 50/60 Hz 0.18 kW at 440 V AC 50/60 Hz
Coordination typeType 2
Device short nameGV2DP
Device composition1 motor circuit breaker type GV2P 1 3-pole contactor 1 combination block GV2AF3
Motor starter typeNon reversing
Breaking capacityIq 130 kA at 400/415 V conforming to IEC 60947-4-1 Iq 130 kA at 440 V conforming to IEC 60947-4-1 Iq 130 kA at 500 V conforming to IEC 60947-4-1
Magnetic tripping current8 A
Thermal protection adjustment range0.4...0.63 A

Product details

The GV2DP104F7 is a non-reversing DOL combination starter from the TeSys Deca range, integrating a GV2P motor circuit breaker, a 3-pole contactor, and a GV2AF3 combination block into one assembly. The thermal protection adjustment range is 0.4 to 0.63 A, and the magnetic tripping current is fixed at 8 A. The coil is rated for 110 VAC at 50/60 Hz.

Rated breaking capacity is 130 kA at 400/415 V, 440 V, and 500 V per IEC 60947-4-1. This is a Type 2 coordination assembly, meaning after a short-circuit fault the starter remains serviceable with no damage to the contactor or overload — no part replacement needed. The 130 kA figure covers most industrial distribution panels without requiring upstream current-limiting fuses.

DIN-rail footprint

Width is 45 mm, height 176.4 mm, depth 105.6 mm. The 45 mm width matches a standard 2.5-module DIN-rail footprint, so it occupies two adjacent 18 mm slots on the rail. Panel builders should verify clearance for the depth — 105.6 mm extends beyond the back of a shallow 120 mm enclosure.

Frequently asked questions

Where can I buy GV2DP104F7?

The GV2DP104F7 is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What is the thermal protection adjustment range for GV2DP104F7?

The thermal protection adjustment range is 0.4 to 0.63 A, set via the dial on the motor circuit breaker section.

What breaking capacity does GV2DP104F7 have?

Rated breaking capacity is 130 kA at 400/415 V, 440 V, and 500 V per IEC 60947-4-1.