The GV2DP104F7 is a non-reversing DOL combination starter from the TeSys Deca range, integrating a GV2P motor circuit breaker, a 3-pole contactor, and a GV2AF3 combination block into one assembly. The thermal protection adjustment range is 0.4 to 0.63 A, and the magnetic tripping current is fixed at 8 A. The coil is rated for 110 VAC at 50/60 Hz.
Rated breaking capacity is 130 kA at 400/415 V, 440 V, and 500 V per IEC 60947-4-1. This is a Type 2 coordination assembly, meaning after a short-circuit fault the starter remains serviceable with no damage to the contactor or overload — no part replacement needed. The 130 kA figure covers most industrial distribution panels without requiring upstream current-limiting fuses.
DIN-rail footprint
Width is 45 mm, height 176.4 mm, depth 105.6 mm. The 45 mm width matches a standard 2.5-module DIN-rail footprint, so it occupies two adjacent 18 mm slots on the rail. Panel builders should verify clearance for the depth — 105.6 mm extends beyond the back of a shallow 120 mm enclosure.