Schneider Electric GV2DP107F7 — Miniature Circuit Breakers (MCB)

Schneider GV2DP107F7 TeSys Deca DOL Starter, 1.6-2.5A, 110VA

MPNGV2DP107F7
Obsolete

Schneider Electric TeSys Deca GV2DP107F7 DOL combination starter, 1.6 to 2.5 A thermal protection range, 110 VAC 50/60 Hz coil, 3-pole non-reversing, Type 2 coordination.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2DP107F7 — Identification
ParameterValue
Product range (series)TeSys Deca
Product/component typeMotor starter
GV2DP107F7 — Ratings
ParameterValue
Poles configuration3P
Utilisation categoryAC-3
GV2DP107F7 — Mechanical
ParameterValue
Width45 mm
Height176.4 mm
Depth105.6 mm
GV2DP107F7 — Other specifications
ParameterValue
Motor power0.75 kW at 400/415 V AC 50/60 Hz 0.75 kW at 440 V AC 50/60 Hz 1.1 kW at 440 V AC 50/60 Hz 1.1 kW at 500 V AC 50/60 Hz
Coordination typeType 2
Device short nameGV2DP
Device composition1 combination block GV2AF3 1 3-pole contactor 1 motor circuit breaker type GV2P
Motor starter typeNon reversing
Breaking capacityIq 130 kA at 400/415 V conforming to IEC 60947-4-1 Iq 130 kA at 440 V conforming to IEC 60947-4-1 Iq 130 kA at 500 V conforming to IEC 60947-4-1
Magnetic tripping current33.5 A
Thermal protection adjustment range1.6...2.5 A

Product details

The Schneider Electric GV2DP107F7 is a direct-on-line (DOL) combination starter from the TeSys Deca range, integrating a 3-pole motor circuit breaker (type GV2P) and a 3-pole contactor into a single block, factory-assembled with a GV2AF3 combination block. It provides coordinated motor starting and overload protection in a compact, non-reversing package. The thermal protection adjustment range of 1.6 to 2.5 A sets the overload relay trip point, matching it to the motor's full-load current. For a 400/415 V supply, this corresponds to a motor power rating of 0.75 kW; at 440 V it also covers 0.75 kW, and at 500 V it reaches 1.1 kW. Rated in utilisation category AC-3 (squirrel-cage motor starting and switching off during running), the starter delivers a rated breaking capacity of 130 kA at 400/415 V, 440 V, and 500 V, conforming to IEC 60947-4-1. The magnetic tripping current is fixed at 33.5 A, providing short-circuit protection coordinated to Type 2 — meaning the contactor and overload relay remain serviceable after a fault at the rated breaking capacity.

The starter measures 45 mm wide, 176.4 mm high, and 105.6 mm deep. The 105.6 mm depth is the dimension from the DIN-rail mounting surface to the furthest projection — check this against the enclosure's internal depth, especially if a door-mounted operator or additional terminal blocks sit behind the panel.

Frequently asked questions

Where can I buy GV2DP107F7 and how do I get a price?

The GV2DP107F7 is sourced through independent distribution channels. Submit an RFQ for this order code; availability and current pricing are confirmed at quote time.

What is GV2DP107F7's thermal protection adjustment range?

The thermal protection adjustment range is 1.6 to 2.5 A, which sets the overload relay trip point to match the motor's full-load current.

What breaking capacity does the GV2DP107F7 provide?

It provides a rated breaking capacity of 130 kA at 400/415 V, 440 V, and 500 V, conforming to IEC 60947-4-1, with Type 2 coordination.