The GV2DP116FE7 is a DOL combination motor starter from the TeSys Deca range — a factory-assembled unit that pairs a GV2P motor circuit breaker, a GV2AF3 combination block, and a 3-pole contactor into one non-reversing starter. It's sized for motor loads in the 9…14 A thermal protection adjustment range, with a 115 V AC 50/60 Hz control coil. The thermal adjustment range (9…14 A) is what you set to match the motor full-load current — the overload relay inside the breaker protects the motor from sustained overcurrent. The magnetic trip is fixed at 170 A, which clears short-circuit faults fast enough to achieve Type 2 coordination, meaning the contactor and downstream components survive a fault without damage. Rated breaking capacity is 130 kA at 400/415 V per IEC 60947-4-1, 50 kA at 440 V, and 42 kA at 500 V — that's the maximum fault current the starter can safely interrupt. The motor power ratings span 5.5 kW at 400/415 V up to 9 kW at 500 V, all in AC-3 duty (starting squirrel-cage motors).
This part is listed as Obsolete by the manufacturer.
The starter measures 45 mm wide, 186.8 mm high, and 111.9 mm deep — a standard compact footprint for a 3-pole combination starter.