The GV2DP132M7 is a DOL combination motor starter from the TeSys Deca range — a factory-assembled unit that pairs a GV2P motor circuit breaker, a 3-pole contactor, and a GV2AF3 combination block in one package. Thermal protection adjusts from 24 to 32 A, and the magnetic trip fires at 416 A, so it catches both overload and short-circuit conditions on a motor branch circuit. Rated for AC-3 duty (squirrel-cage motor switching), it delivers 15 kW at 400/415 V and 440 V, and 18.5 kW at 500 V. The coil is 220 V AC 50/60 Hz. Panel footprint: 45 mm wide, 186.8 mm tall, 111.9 mm deep — fits a standard 45 mm slot on a DIN rail or backplate.
Schneider TeSys Deca GV2DP132M7 DOL Starter, 24-32A, 220VAC
Schneider Electric TeSys Deca GV2DP132M7, DOL non-reversing motor starter, 24...32 A thermal adjustment, 220 V AC 50/60 Hz coil, 3-pole, Type 2 coordination.
Specifications
| Parameter | Value |
|---|---|
| Product range (series) | TeSys Deca |
| Product/component type | Motor starter |
| Parameter | Value |
|---|---|
| Poles configuration | 3P |
| Utilisation category | AC-3 |
| Parameter | Value |
|---|---|
| Width | 45 mm |
| Height | 186.8 mm |
| Depth | 111.9 mm |
| Parameter | Value |
|---|---|
| Motor power | 15 kW at 400/415 V AC 50/60 Hz 15 kW at 440 V AC 50/60 Hz 18.5 kW at 500 V AC 50/60 Hz |
| Coordination type | Type 2 |
| Device short name | GV2DP |
| Device composition | 1 3-pole contactor 1 motor circuit breaker type GV2P 1 combination block GV2AF3 |
| Motor starter type | Non reversing |
| Breaking capacity | Iq 50 kA at 400/415 V conforming to IEC 60947-4-1 Iq 20 kA at 440 V conforming to IEC 60947-4-1 Iq 10 kA at 500 V conforming to IEC 60947-4-1 |
| Magnetic tripping current | 416 A |
| Coil voltage | 220 V AC 50/60 Hz |
| Thermal protection adjustment range | 24...32 A |
Product details
Frequently asked questions
Where can I buy GV2DP132M7?
Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.
What is the thermal protection range of GV2DP132M7?
The thermal adjustment range is 24 to 32 A, set via the dial on the motor circuit breaker section.
What breaking capacity does GV2DP132M7 have?
Rated breaking capacity is 50 kA at 400/415 V, 20 kA at 440 V, and 10 kA at 500 V, all per IEC 60947-4-1.
What motor power does GV2DP132M7 support?
15 kW at 400/415 V and 440 V, 18.5 kW at 500 V, all at 50/60 Hz, AC-3 duty.