The GV2DP106F7 is a direct-on-line (DOL) combination motor starter from the TeSys Deca range, integrating a 3-pole motor circuit breaker (GV2P type) and a 3-pole contactor into one compact block with the GV2AF3 interconnection kit. It is non-reversing and rated for AC-3 utilization category, meaning it is built for starting and stopping squirrel-cage induction motors under load — not for resistive heating or DC loads. Thermal protection adjusts from 1 to 1.6 A, and the magnetic trip is fixed at 22.5 A. That combination covers small motors — think fractional-horsepower pumps, fans, or conveyors on 400/415 V or 440 V supplies where the motor full-load current falls inside that window. The coil is 110 VAC 50/60 Hz, so it drops into control circuits running that voltage. The 130 kA rated breaking capacity (Iq) at 400/415 V, 440 V, and 500 V per IEC 60947-4-1 means this starter can safely interrupt fault currents up to that level — essential for Type 2 coordination where downstream damage must be limited after a short circuit.
The starter measures 45 mm wide, 176.4 mm high, and 105.6 mm deep. Depth of 105.6 mm means it clears most 120 mm deep enclosures, but check the door clearance if a rotary handle or enclosure door protrusion is planned.