Schneider Electric GV4L07N6 — Motor Protection Circuit Breakers (MPCB)

Schneider Electric GV4L07N6 TeSys GV4 Motor Circuit Breaker,

MPNGV4L07N6
Active

Schneider Electric TeSys GV4 motor circuit breaker, GV4L07N6, 3-pole, 7 A rated current, 100 kA breaking capacity at 240 V AC, magnetic-electronic trip.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GV4L07N6 — Mechanical
ParameterValue
Height155 mm
Width81 mm
Depth165 mm

Product details

Motor power coverage and trip characteristics

The GV4L07N6: This 7 A frame covers a wide motor power band depending on line voltage: 1.5 kW at 400 V, up to 4 kW at 500 V, and as high as 7.5 kW at 690 V. The magnetic trip threshold is adjustable between 42 and 98 A — that is the short-circuit / instantaneous trip, not the overload. The electronic overload element handles the thermal curve. The utilisation category is AC-3 (squirrel-cage motor starting) per IEC 60947-4-1, which is the standard for direct-on-line motor starting.

Durability and environmental ratings for continuous duty

Rated for continuous duty per IEC 60947-4-1. Electrical durability is 40,000 cycles at AC-3 at 440 V, both at In and at In/2 — that is the number of motor starts before the contacts need replacement. Mechanical durability matches at 40,000 cycles. The maximum operating rate is 25 cycles per hour, so it is sized for a machine that starts a motor every couple of minutes, not a high-speed jogging application. The enclosure is IP40 (finger-safe, no water ingress protection) and IK07 (impact resistance up to 2 J).

Integration into the panel: dimensions, connections, and isolation

Dimensions are 155 mm high, 81 mm wide, and 165 mm deep. The connection pitch is 27 mm without spreaders, 35 mm with spreaders — this matters when laying out multiple breakers on a DIN rail for busbar connection. Terminals accept lugs or ring terminals; tightening torque is 9 N·m for the main power cables (16–95 mm²) and 5 N·m for control wiring (1.5–10 mm²). Operating position is any, and the altitude rating goes to 5000 m, so it works in high-altitude installations without derating.

Frequently asked questions

What is the breaking capacity of the GV4L07N6?

The breaking capacity (Icu) is 100 kA at 220–240 V AC, 50 kA at 380–415 V AC, 50 kA at 440 V AC, 25 kA at 500 V AC, 15 kA at 525 V AC, and 8 kA at 660–690 V AC, all per IEC 60947-2.

What motor power can the GV4L07N6 protect?

At 400–415 V AC, it covers 1.5 kW to 3 kW. At 500 V AC, it covers 2.2 kW to 4 kW. At 660–690 V AC, it covers 3 kW to 7.5 kW.

What standards does the GV4L07N6 comply with?

It complies with EN/IEC 60947-4-1 (motor protection) and EN/IEC 60947-2 (circuit breakers). It is also suitable for isolation per IEC 60947-1.

MPN
GV4L07N6