Its AC-1 utilisation category rates it for 125 A resistive loads, and the motor power table covers induction motors from 22 kW at 230 V up to 55 kW at 500 V. The coil is AC 50/60 Hz without a built-in suppressor module; external suppression is required if switching inductive control circuits. Coil hold power is 245 VA inrush at 20 °C, steady-state heat dissipation 6–10 W.
The contactor carries certifications under IEC 60947-4-1, IEC 60947-5-1, CSA C22.2 No 14, and UL 60947-4-1, so it meets North American and international standards for industrial control equipment.
Mounts on a plate or 35 mm DIN rail. Power circuit wiring accepts 4–50 mm² flexible with cable end, and tightening torque is 106.2 lbf·in (12 N·m) for the power terminals. Mechanical durability is 4 million cycles, electrical durability 0.8 million cycles at 125 A AC-1, 440 V. Maximum operating rate is 3600 cycles per hour at 60 °C.