Skip to main content
Schneider Electric LC1F150P5 — Contactors

Schneider Electric LC1F150P5 TeSys F Contactor, 250 A AC-3,

MPNLC1F150P5
Obsolete

Schneider Electric TeSys F series, LC1F150P5, 3-pole contactor, 250 A rated operational current (AC-3), 230 V AC 50 Hz coil, plate mount, 171 x 163.5 x 170 mm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1F150P5 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationMotor control Resistive load
LC1F150P5 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-4 AC-1 AC-3
LC1F150P5 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1F150P5 — Environmental
ParameterValue
IP degree of protectionIP2X front face with shrouds conforming to IEC 60529 IP2X front face with shrouds conforming to VDE 0106
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH
LC1F150P5 — Approvals
ParameterValue
StandardsIEC 60947-4-1 IEC 60947-1 EN 60947-4-1 EN 60947-1 JIS C8201-4-1
LC1F150P5 — Mechanical
ParameterValue
Width163.5 mm
Height170 mm
Depth171 mm

Product details

The LC1F150P5: The 250 A AC-3 rating governs motor switching — that's the current the contactor can make and break across a typical induction motor load. For resistive heating (AC-1), the thermal current Ith is 250 A at 50 Hz, with 22 W dissipation per pole. The 0.35 mOhm average impedance per pole at 250 A gives a voltage drop worth checking against your load's minimum operating voltage.

Plate-mounted, not DIN-rail — plan for a drilled backplate or sub-panel. Dimensions are 171 mm deep, 163.5 mm wide, 170 mm tall. Power connections accept bar (25 x 3 mm busbar), ring lugs up to 120 mm², or bolted connection. Control wiring uses screw clamp terminals, 1 to 4 mm² flexible or solid. Torque power circuit connections to 18 N·m, control circuit to 1.2 N·m. Front face with shrouds achieves IP2X.

Standards and Environmental Range

Certified to IEC 60947-4-1 and EN 60947-4-1, the standard for contactors and motor-starters. Rated insulation voltage is 1000 V per IEC 60947-4-1, 1500 V per VDE 0110 Group C. Overvoltage category III suits fixed-installation distribution panels. Protective treatment is TH (tropicalized) for humid environments.

Frequently asked questions

What motor power can the LC1F150P5 handle?

Motor power depends on supply voltage: 75 kW at 380-400 V, 80 kW at 415 V and 440 V, 90 kW at 500 V, 100 kW at 660-690 V, all in AC-3 duty at 50/60 Hz.

What standards does the LC1F150P5 comply with?

It complies with IEC 60947-4-1, IEC 60947-1, EN 60947-4-1, EN 60947-1, and JIS C8201-4-1.

MPN
LC1F150P5