Skip to main content
Schneider Electric LC1F185FE5 — Contactors

Schneider Electric LC1F185FE5 TeSys F Contactor, 275 A, 115

MPNLC1F185FE5
Obsolete

Schneider Electric TeSys F, LC1F185FE5, 3-pole contactor, 275 A rated operational current (AC-3), 115 V AC 50 Hz coil, plate mount, 181 mm depth.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1F185FE5 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load Motor control

Ratings & Performance

LC1F185FE5 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 690 V AC 50/60 Hz
Utilisation categoryAC-3 AC-1

Contacts & Poles

LC1F185FE5 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC1F185FE5 — Environmental
ParameterValue
IP degree of protectionIP2X front face with shrouds conforming to IEC 60529 IP2X front face with shrouds conforming to VDE 0106
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH

Approvals

LC1F185FE5 — Approvals
ParameterValue
StandardsIEC 60947-4-1 JIS C8201-4-1 EN 60947-4-1 IEC 60947-1 EN 60947-1

Mechanical

LC1F185FE5 — Mechanical
ParameterValue
Width168.5 mm
Height174 mm
Depth181 mm

Product details

The Schneider Electric LC1F185FE5 is a 3-pole TeSys F contactor with a 115 V AC 50 Hz coil, rated for 275 A operational current in AC-3 duty (motor switching) and built to IEC 60947-4-1. It handles motor loads up to 90 kW at 380–400 V and 110 kW at 500 V AC-3, making it a fit for medium-voltage motor control centers and heavy conveyor or pump drives. Plate-mount construction means it lands on a backplate or sub-panel, not a DIN rail — plan the enclosure layout accordingly.

The AC-1 rating (resistive load) is higher, but for motor duty, stick with the AC-3 figure. Mechanical durability is 10 million cycles, so in a moderate-duty application (one or two operations per minute) it'll outlast the panel. Coil hold-in power is 55 VA at 50 Hz; the inrush is 805 VA — ensure your control transformer can handle that surge on pickup.

Integration notes — plate mount, wiring, environment

Mounts on a plate (not DIN rail). Power circuit terminals accept bar (25 x 3 mm busbar), ring lugs up to 150 mm², or connectors for 150 mm² cable. Control circuit uses screw clamp terminals, 1–4 mm² flexible or solid. Torque: 18 N·m on power, 1.2 N·m on control. Altitude rating is 3000 m without derating. IP2X front face with shrouds — not washdown-rated, so keep it in a cabinet.

Frequently asked questions

What are the key specifications of LC1F185FE5?

It is a 3-pole TeSys F contactor with a 115 V AC 50 Hz coil, rated 275 A in AC-3 duty at ≤ 440 V, and switches motor loads up to 110 kW at 500 V AC-3. It complies with IEC 60947-4-1 and EN 60947-4-1.

MPN
LC1F185FE5