Skip to main content
Schneider Electric LC1F2100F7 — Contactors

Schneider Electric LC1F2100F7 TeSys F Contactor, 2100 A AC-1

MPNLC1F2100F7
Obsolete

Schneider Electric TeSys F LC1F2100F7, 3-pole contactor, 2100 A AC-1, 110 V AC 40-400 Hz control circuit, plate mount, EOL lifecycle.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1F2100F7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load

Ratings & Performance

LC1F2100F7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1

Contacts & Poles

LC1F2100F7 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC1F2100F7 — Environmental
ParameterValue
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH

Approvals

LC1F2100F7 — Approvals
ParameterValue
StandardsIEC 60947-4-1 EN 60947-1 EN 60947-4-1 IEC 60947-1 JIS C8201-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1

Mechanical

LC1F2100F7 — Mechanical
ParameterValue
Width438 mm
Height332 mm
Depth238.6 mm

Product details

The LC1F2100F7 is a 3-pole TeSys F contactor rated for 2100 A conventional free-air thermal current (Ith) and 2100 A operational current in AC-1 utilisation category — meaning it is sized for resistive heating loads, not motor starting. AC-1 duty covers loads where the current waveform stays nearly sinusoidal with no significant inrush, such as large electric furnaces, banked heaters, or power-factor correction capacitor banks. The 110 V AC control circuit (40-400 Hz) draws 2200 VA inrush and holds at 36 VA; dropout occurs between 0.3 and 0.5 Uc, so the coil reliably releases below about 55 V AC. Rated breaking capacity is 3150 A per IEC 60947-4-1, and the short-time withstand current (Icw) reaches 10 kA for 10 seconds — enough to coordinate with upstream 2000 A gG fuses at ≤ 440 V without nuisance opening during a downstream fault. The contactor carries overvoltage category III and an impulse withstand voltage of 8 kV, so it suits fixed-installation distribution panels where transient overvoltages from the mains are expected.

The contactor is certified to IEC 60947-4-1, EN 60947-1, EN 60947-4-1, JIS C8201-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C. The protective treatment (TH) indicates suitability for tropical/humid environments. Operating altitude reaches 3000 m without derating.

Mounts on a plate (not DIN rail) — the 438 mm width and 332 mm height require a dedicated backplate in the enclosure. Power connections use bolted bars accepting up to 100 x 5 mm busbars; control circuit connections are screw-clamp terminals accepting 1…4 mm² flexible or solid wire. Tightening torque is 58 N.m on the power circuit and 1.2 N.m on the control circuit. Heat dissipation is 36 W total (200 W per pole in AC-1), so forced ventilation or derating may be needed in a sealed cabinet above 40 °C ambient.

Frequently asked questions

Who supplies LC1F2100F7 and how is it quoted for volume purchases?

This part is sourced through independent distribution channels. Availability and current pricing are confirmed at quote time against an RFQ — no stock count or price is listed here.

What is the closest pin-compatible alternative to LC1F2100F7 in this component family?

No official successor order code is listed in the lifecycle record. A form-fit-function cross-reference would need to be evaluated against the original panel design, considering the 2100 A AC-1 rating, 110 V AC coil, and plate-mount footprint.

What compliance documentation does this brand provide for LC1F2100F7?

The contactor carries certifications to IEC 60947-4-1, EN 60947-1, EN 60947-4-1, JIS C8201-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C.

MPN