Skip to main content
Schneider Electric LC1F6304P7 — Contactors

Schneider LC1F6304P7 TeSys F Contactor, 1000 A AC-1, 4 NO, 2

MPNLC1F6304P7
Obsolete

Schneider Electric TeSys F, LC1F6304P7, 4-pole contactor, 1000 A AC-1, 230 V AC 40-400 Hz coil, plate mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC1F6304P7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load
LC1F6304P7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1
LC1F6304P7 — Contacts & Poles
ParameterValue
Pole configuration4P
LC1F6304P7 — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH
LC1F6304P7 — Approvals
ParameterValue
StandardsEN 60947-1 IEC 60947-1 JIS C8201-4-1 IEC 60947-4-1 EN 60947-4-1
LC1F6304P7 — Mechanical
ParameterValue
Width389 mm
Height304 mm
Depth255 mm

Product details

The Schneider Electric LC1F6304P7 is a TeSys F 4-pole contactor rated for 1000 A in AC-1 utilisation category at ≤440 V, 40 °C — meaning it is sized for switching resistive loads such as large heating banks or furnace elements, not motor starting. The 230 V AC coil (40–400 Hz) draws 1650 VA inrush and 22 VA hold-in. Four normally-open power poles handle the full current path. Mounts on a plate (not DIN rail), with power connections via busbar (60 x 5 mm cross-section) or bolted connection. The IP20 front face with shrouds meets IEC 60529 and VDE 0106 for finger-safe panel integration. Rated breaking capacity is 5040 A per IEC 60947-4-1, and the rated insulation voltage is 1000 V (IEC 60947-4-1) or 1500 V (VDE 0110 Group C). Impulse withstand voltage is 8 kV, overvoltage category III.

The 1000 A AC-1 rating governs the continuous resistive load it can carry. For comparison, a motor load (AC-3) would derate significantly — this contactor is not selected for motor duty. The 4 NO pole configuration means all four poles switch the line; there are no built-in auxiliary contacts, so an external auxiliary block is needed for control-circuit feedback. Associated fuse rating is 1000 A gG or 630 A aM at ≤440 V — the gG (general-purpose) fuse protects against overload and short-circuit; the aM (motor-circuit) fuse is for backup protection only. The 5 Mcycle mechanical durability and 1200 cycles/hour maximum operating rate at 55 °C indicate a heavy-duty switching schedule for process applications. Operating time is 40–80 ms closing, 100–200 ms opening. Heat dissipation is 20 W total (120 W per pole in AC-1).

Physical integration and wiring

Dimensions: 389 mm wide, 304 mm high, 255 mm deep. Plate-mounted — ensure the backplate has clearance for the 255 mm depth plus busbar connections. Power circuit tightening torque is 58 N.m; control circuit is 1.2 N.m. Control wiring accepts 1–4 mm² flexible or solid, with or without ferrules, via screw clamp terminals. Altitude derating begins above 3000 m. The TH protective treatment indicates the contactor is suitable for tropical/humid environments.

Frequently asked questions

What is the rated current of LC1F6304P7?

The LC1F6304P7 is rated for 1000 A in AC-1 utilisation category at ≤440 V, 40 °C. This is for resistive loads only.

What is the control voltage for this contactor?

The control circuit voltage is 230 V AC, 40–400 Hz. The coil operates between 0.85 and 1.1 Uc and drops out between 0.25 and 0.5 Uc at 55 °C.

Where can I buy LC1F6304P7?

As an end-of-life part, the LC1F6304P7 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What standards does LC1F6304P7 comply with?

The contactor complies with EN 60947-1, IEC 60947-1, JIS C8201-4-1, IEC 60947-4-1, and EN 60947-4-1. The IP20 front face conforms to IEC 60529 and VDE 0106.

MPN