Schneider Electric LC3F225FE7A64 — Contactors

Schneider Electric LC3F225FE7A64 TeSys F Star Delta Starter,

MPNLC3F225FE7A64
Obsolete

Schneider Electric TeSys F, LC3F225FE7A64, star delta starter, 225 A AC-3, 115 V AC 50/60 Hz coil, 3 x 3P poles, pre-wired.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC3F225FE7A64 — Identification
ParameterValue
Product / component typeStar delta starter
Series / rangeTeSys
ApplicationMotor control
LC3F225FE7A64 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: <= 1000 V AC 16 Hz 2/3...200 Hz
Utilisation categoryAC-3
LC3F225FE7A64 — Contacts & Poles
ParameterValue
Pole configuration3 x 3P
LC3F225FE7A64 — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open: 2 Gn, 5...300 Hz Shocks contactor closed: 15 Gn for 11 ms Vibrations contactor closed: 5 Gn, 5...300 Hz Shocks contactor open: 7 Gn for 11 ms
Protective treatment / pollution degreeTH
LC3F225FE7A64 — Approvals
ParameterValue
StandardsEN 60947-4-1 JIS C8201-4-1 EN 60947-1 IEC 60947-1 IEC 60947-4-1
LC3F225FE7A64 — Mechanical
ParameterValue
Width525 mm
Height110 mm
Depth235 mm

Product details

It switches a 225 A rated operational current at ≤440 V AC (AC-3), handling motor loads up to 200 kW at 380/400 V AC or 220 kW at 440 V AC. The 115 V AC 50/60 Hz control coil pulls 805 VA inrush at 50 Hz, 970 VA at 60 Hz. Mechanical interlocking between the star, line, and delta contactors prevents simultaneous closure — a standard safeguard for star-delta transition.

The 225 A AC-3 rating at ≤440 V defines the motor-switching capacity under IEC 60947-4-1. For a 200 kW motor at 400 V, this starter handles the locked-rotor inrush and breaks the running current without welding contacts. The 115 V AC coil (0.85–1.1 Uc operational range) is standard for North American and many European control circuits — verify your panel's control transformer matches. The 3 x 3P pole configuration (three NO power poles per contactor) is built for three-phase star-delta transition; the auxiliary contact composition includes 1 NO + 1 NC for the star contactor, 1 NO + 2 NC for the line contactor, and 2 NO + 1 NC for the delta contactor — enough for self-holding and status feedback without adding an aux block.

This is a plate-mounted unit (not DIN-rail), sized 525 mm wide × 110 mm high × 235 mm deep. The power circuit terminates on M10 bolted connections accepting busbars up to 32 × 4 mm or lugs up to 185 mm². Control wiring uses screw clamp terminals accepting 1–4 mm² flexible or solid. The IP20 front face (with shrouds) suits enclosed panel installation — not washdown environments.

Frequently asked questions

What are the key ratings for this star delta starter?

Rated operational current 225 A AC-3 at ≤440 V, motor power up to 200 kW at 380/400 V AC, control coil 115 V AC 50/60 Hz, mechanical durability 10 million cycles.

What standards does the LC3F225FE7A64 comply with?

It complies with IEC 60947-4-1, IEC 60947-1, EN 60947-4-1, EN 60947-1, and JIS C8201-4-1.

What is the depth of this starter?

The depth is 235 mm.