It's rated 125 A continuous and carries switch-disconnector fuse protection, meaning the disconnect and fuse block are integrated into the same package — one SKU for the panel builder, not a separate fusible switch plus contactor assembly.
Horsepower coverage — what motor it drives
The horsepower table spans single-phase and three-phase motors: 7.5 hp at 120 VAC single-phase, 15 hp at 240 VAC single-phase, 25 hp at 208 VAC three-phase, 30 hp at 230 VAC three-phase, and 60 hp at both 460 VAC and 575 VAC three-phase. That 60 hp at 575 VAC is the ceiling — common for 600 V class industrial lines in North America.
Control voltage and auxiliary contacts
Coil is 120 VAC 50/60 Hz, which is the standard control voltage for most North American panels. The starter ships with one normally-open and one normally-closed auxiliary contact built in — enough to seal in the starter and send a status signal back to the PLC without adding an aux block.