Skip to main content
Schneider Electric LP1K12016BD3 — Contactors

Schneider Electric LP1K12016BD3 TeSys K Contactor, 12A, 24V

MPNLP1K12016BD3
Obsolete

Schneider Electric TeSys K contactor, 3P, 12 A AC-3/AC-3e at 440 V, 24 V DC coil with integral suppression, 1 NC auxiliary.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LP1K12016BD3 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationMotor control Resistive load
LP1K12016BD3 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-3e AC-1 AC-4
LP1K12016BD3 — Contacts & Poles
ParameterValue
Pole configuration3P
LP1K12016BD3 — Environmental
ParameterValue
IP degree of protectionIP2X
Operating altitude2000 m without derating
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LP1K12016BD3 — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 UL 60947-5-1 CSA C22.2 No 60947-4-1 CSA C22.2 No 60947-5-1 GB/T 14048.4
LP1K12016BD3 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The LP1K12016BD3 is a 3-pole TeSys K contactor from Schneider Electric, rated 12 A in AC-3 and AC-3e utilisation categories at 440 V, with a 24 V DC coil that includes an integral suppression device. It carries one normally closed instantaneous auxiliary contact. This size fits into the compact TeSys K footprint — 45 mm wide, 58 mm high, 57 mm deep — and mounts to either a plate or DIN rail, so it slots into a standard control-panel layout without eating up extra rail space.

The AC-3 rating at 12 A / 440 V is the motor-switching figure that governs real-world use — it handles squirrel-cage motors up to roughly 5.5 kW at 400 V. The AC-1 resistive rating goes higher (20 A), but for motor loads the AC-3 number is the one to match against your BOM. Electrical durability is 1.3 million cycles at the AC-3 rating; mechanical durability is 10 million cycles, so this contactor is built for moderate-duty cycling applications like conveyors or small pumps.

This part is officially obsolete per the manufacturer. There is no listed direct successor order code in the evidence.

Installation and integration notes

Terminals accept ring lugs with a 7 mm outer diameter. The IP2X finger-safe front cover is built in.

Frequently asked questions

What are the key ratings for this contactor?

It is a 3-pole contactor rated 12 A in AC-3/AC-3e at 440 V, with a 24 V DC coil drawing 3 W. It includes one NC auxiliary contact and an integral coil suppression device.

What compliance documentation does this part carry?

It is certified to EN/IEC 60947-4-1 and -5-1, UL 60947-4-1 and -5-1, CSA C22.2 No 60947-4-1 and -5-1, and GB/T 14048.4. Flame retardance is V1 per UL 94.

MPN
LP1K12016BD3