Skip to main content
Schneider Electric LV846215 — Air Circuit Breakers

Schneider Electric LV846215 MasterPact MTZ2 2500 A Circuit B

MPNLV846215
Active

Schneider Electric MasterPacT MTZ2, LV846215, 4P drawout circuit breaker, 2500 A at 40 °C, H2V 100 kA 415 V AC performance.

$11,204.46Ref. price · indicative, final on quote
StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV846215 — Identification
ParameterValue
Product typeCircuit breaker
Product nameMasterPact MTZ2
RangeMasterPacT
ApplicationPower distribution protection
Control unitWithout control unit

Electrical ratings

LV846215 — Electrical ratings
ParameterValue
Rated current (In)2500 A at 40 °C
Sensor rating1250 A 1600 A 2000 A 2500 A
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)12 kV
Suitable for isolationYes conforming to EN/IEC 60947-2

Breaking & withstand capacity

LV846215 — Breaking & withstand capacity
ParameterValue
Rated ultimate breaking capacity (Icu)100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz
Rated service breaking capacity (Ics)100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz
Rated short-time withstand current (Icw)100 kA 0.5 s 100 kA 1 s 75 kA 3 s
Rated short-circuit making capacity (Icm)220 kA 220/415 V AC at 50/60 Hz 220 kA 440 V AC at 50/60 Hz
Performance typeH2V 100 kA 415 V AC

Performance

LV846215 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)15000 cycles with periodic preventive maintenance
Electrical durability (cycles)5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23A: 5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3
Selectivity categoryCategory B
Power dissipation600 W

Mechanical & connection

LV846215 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRails Base plate
Width556 mm
Height439 mm
Depth403 mm
Neutral pole positionRight
Connection pitch115 mm
Upside connectionFront Rear
Downside connectionFront Rear

Environmental

LV846215 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP30 conforming to EN 60529
Pollution degree3 conforming to IEC 60947-1
Operating altitude0...2000 m without derating 2000...5000 m with derating

Approvals

LV846215 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12

Product details

MasterPact MTZ2 2500 A — what this breaker delivers

The Schneider Electric LV846215 is a MasterPact MTZ2 drawout circuit breaker rated 2500 A at 40 °C, 4 poles, with H2V performance class delivering 100 kA breaking capacity at 415 V AC. It's built for main incoming or large feeder protection in power distribution — the kind of install where selectivity and fault clearance speed decide uptime. Category B selectivity means it coordinates with downstream breakers to isolate only the faulted branch, keeping the rest of the plant live. The 25 ms maximum break time and 220 kA making capacity tell you it handles high-energy faults without cascading upstream — critical for switchboard integrity. Rated insulation voltage is 1000 V AC, operational voltage 440 V AC, with impulse withstand at 12 kV. The short-time withstand rating (Icw) holds 100 kA for 1 second — enough for full-selectivity schemes with downstream breakers clearing in their own time band.

Drawout mounting and panel integration

Drawout chassis means the breaker slides out for inspection or replacement without disturbing the bus connections — a standard requirement for main breakers in industrial switchgear. Mounting support is rails or base plate; connection pitch is 115 mm. Dimensions: 556 mm wide, 439 mm high, 403 mm deep. That depth matters when you're laying out the cabinet — make sure the drawout rail has clearance for the full travel. IP30 protection is typical for indoor switchgear; no special sealing for washdown environments. Neutral position is right.

Operating altitude 0–2000 m without derating, 2000–5000 m with derating. Ambient temperature range: -25 to 70 °C operating, -40 to 85 °C storage. Power dissipation at rated current is 600 W — factor that into the switchgear ventilation calculation.

Frequently asked questions

What is the breaking capacity of LV846215?

The H2V performance class delivers 100 kA rated service breaking capacity (Ics) at 440 V AC 50/60 Hz, and 100 kA at 220/415 V AC. The rated short-circuit making capacity (Icm) is 220 kA at 440 V AC.

What standards does LV846215 comply with?

Compliant with EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. Suitability for isolation is confirmed per EN/IEC 60947-2.

MPN
LV846215