Specifications

LV847200 — Identification
ParameterValue
Product typeCircuit breaker
Product nameMasterPact MTZ1
RangeMasterPacT
ApplicationPower distribution protection
Control unitWithout control unit
LV847200 — Electrical ratings
ParameterValue
Rated current (In)630 A at 40 °C
Sensor rating400 A 630 A
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)12 kV
Suitable for isolationYes conforming to EN/IEC 60947-2
LV847200 — Breaking & withstand capacity
ParameterValue
Rated ultimate breaking capacity (Icu)42 kA at 220/415 V AC 50/60 Hz 42 kA at 440 V AC 50/60 Hz 42 kA at 500/525 V AC 50/60 Hz 42 kA at 660/690 V AC 50/60 Hz
Rated service breaking capacity (Ics)42 kA at 220/415 V AC 50/60 Hz 42 kA at 440 V AC 50/60 Hz 42 kA at 500/525 V AC 50/60 Hz 42 kA at 660/690 V AC 50/60 Hz
Rated short-time withstand current (Icw)42 kA 0.5 s 42 kA 1 s 24 kA 3 s
Rated short-circuit making capacity (Icm)88 kA 220/415 V AC at 50/60 Hz 88 kA 440 V AC at 50/60 Hz 88 kA 500/525 V AC at 50/60 Hz 88 kA 660/690 V AC at 50/60 Hz
Performance typeH1 42 kA 415 V AC
LV847200 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.50 ms
Mechanical durability (cycles)12500 cycles with periodic preventive maintenance
Electrical durability (cycles)3000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23A: 3000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3
Selectivity categoryCategory B
Power dissipation55 W
LV847200 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRails Base plate
WidthDrawout circuit breaker with chassis: 288 mm Drawout circuit breaker without chassis: 236.5 mm
HeightDrawout circuit breaker with chassis: 322 mm Drawout circuit breaker without chassis: 259.5 mm
DepthDrawout circuit breaker with chassis: 291 mm Drawout circuit breaker without chassis: 207.5 mm
Connection pitch70 mm
Upside connectionFront Rear
Downside connectionFront Rear
LV847200 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP30 conforming to EN 60529
Pollution degree3 conforming to IEC 60947-1
Operating altitude0...2000 m without derating 2000...5000 m with derating
LV847200 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12

Product details

The LV847200 is a Schneider Electric MasterPact MTZ1 drawout circuit breaker, 3-pole, rated 630 A at 40 °C. The Icw of 42 kA for 1 second confirms it withstands delayed-tripping coordination schemes common in selectivity studies. Drawout mounting means the breaker chassis stays wired to the bus while the removable cradle isolates for maintenance or swap — no need to disconnect power cables. Category B selectivity and suitability for isolation (per EN/IEC 60947-2) mean it can serve as the main incoming device in a distribution board where coordination with downstream breakers is required.

Integration notes

The breaker ships without a control unit (specified separately). Mounting support options include rails or a base plate. IP30 enclosure protection is standard; for panel environments with higher dust or moisture ingress, consider an enclosure upgrade. Power dissipation is 55 W — factor this into enclosure thermal calculations, especially in dense switchboards where multiple breakers stack. Altitude derating applies above 2000 m.

Electrical durability is 6000 cycles at 440 V AC (AC-23A) and 3000 cycles at 690 V AC; mechanical durability is 12,500 cycles with periodic preventive maintenance. Maximum breaking time is 25 ms, closing response time 50 ms.

Frequently asked questions

How do I get pricing and availability for LV847200?

The LV847200 is sourced and quoted to order against an RFQ through independent distribution; current pricing and availability are confirmed at quote time.

What is the rated current and breaking capacity of LV847200?

The LV847200 is rated 630 A at 40 °C with an ultimate breaking capacity (Icu) and service breaking capacity (Ics) of 42 kA at 415 V AC. Short-time withstand (Icw) is 42 kA for 1 second.

What compliance standards does LV847200 meet?

The LV847200 is certified to EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. It is suitable for isolation and rated for pollution degree 3.

MPN