Skip to main content
Schneider Electric LV848060 — Circuit Breaker Accessories

Schneider Electric LV848060 MasterPact MTZ2 20 H1, 2000 A, 4

MPNLV848060
Active

Schneider Electric MasterPact MTZ2 20 H1, fixed circuit breaker, 4P, 2000 A at 40 °C, 66 kA breaking at 415 V AC, IP30.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LV848060 — Identification
ParameterValue
Product / component typeCircuit breaker
Product nameMasterPact MTZ2
Product rangeMasterPacT
Device applicationPower distribution protection
LV848060 — Electrical
ParameterValue
Rated current [In]2000 A at 40 °C
Rated operational voltage [Ue]690 V AC 50/60 Hz
Rated insulation voltage [Ui]1000 V AC 50/60 Hz
Rated impulse withstand voltage [Uimp]12 kV
Poles description4P
LV848060 — Protection & Performance
ParameterValue
Rated service breaking capacity [Ics]66 kA at 220/415 V AC 50/60 Hz 66 kA at 440 V AC 50/60 Hz 66 kA at 500/525 V AC 50/60 Hz 66 kA at 660/690 V AC 50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Mechanical durability20000 cycles with periodic preventive maintenance
Electrical durabilityAC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3 6000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 8000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23A: 6000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 8000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3
LV848060 — Mechanical
ParameterValue
Connection pitch115 mm
Downside connectionFront Rear
Upside connectionFront Rear
Device short nameMTZ2 20 H1
Control typePush-button
Mounting modeFixed
Mounting supportRails Base plate
Width537 mm
Height352 mm
Depth300 mm
LV848060 — Environmental
ParameterValue
IP degree of protectionIP30 conforming to EN 60529
Pollution degree3 conforming to IEC 60947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-40...85 °C
LV848060 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12

Product details

MasterPact MTZ2 20 H1 — 2000 A fixed breaker, Category B selectivity

The Schneider Electric LV848060 is a MasterPact MTZ2 20 H1 fixed-mount circuit breaker, 4-pole, rated 2000 A continuous at 40 °C. This is the H1 performance variant, delivering 66 kA rated service breaking capacity (Ics) at 415 V AC — the same figure holds across 440 V, 500/525 V, and 660/690 V AC, so you don't lose headroom at higher voltages. Category B selectivity (per EN/IEC 60947-2) means it's designed for full discrimination with downstream breakers, critical for minimizing outage scope in a distribution board. Rated short-time withstand (Icw) is 66 kA for 0.5 s and 1 s, dropping to 36 kA at 3 s — that 1-second window covers most delayed-tripping coordination schemes. Making capacity (Icm) hits 145 kA at 415 V, confirming the breaker can close into a full fault without contact welding. Mechanical durability is 20,000 cycles with periodic preventive maintenance; electrical endurance under AC-3 motor-switching duty is 6,000 cycles at 690 V.

Fixed-mount chassis, 352 mm high × 537 mm wide × 300 mm deep. Connection pitch is 115 mm. Upside and downside connections accept both front and rear terminations, giving flexibility for busbar or cable entry in a switchboard. Mounts on rails or a base plate — typical for a dedicated MCC or distribution section.

Also complies with IEC 61557-12 for insulation monitoring. Rated insulation voltage (Ui) 1000 V AC, rated impulse withstand (Uimp) 12 kV.

Frequently asked questions

Where can I buy LV848060 and how do I get a price?

Sourced and quoted to order against an RFQ through independent distribution. Submit a request for current pricing and availability.

What is LV848060's breaking capacity at 415 V?

66 kA rated service breaking capacity (Ics) at 220/415 V AC, 440 V, 500/525 V, and 660/690 V AC. Making capacity (Icm) is 145 kA at 415 V.

What compliance documentation does this brand provide for LV848060?

Certified to EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. Suitability for isolation is confirmed per EN/IEC 60947-2.

MPN
LV848060