Skip to main content
Schneider Electric LV848187 — Circuit Breaker Accessories

Schneider Electric LV848187 MasterPact MTZ2 32 H1, 3200 A, 4

MPNLV848187
Active

Schneider Electric MasterPact MTZ2 series, LV848187, fixed-mount power circuit breaker, 3200 A rated current, 4 poles, H1 66 kA breaking performance at 415 V AC.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV848187 — Identification
ParameterValue
Product / component typeCircuit breaker
Product nameMasterPact MTZ2
Product rangeMasterPacT
Device applicationPower distribution protection

Electrical

LV848187 — Electrical
ParameterValue
Rated current [In]3200 A at 40 °C
Rated operational voltage [Ue]690 V AC 50/60 Hz
Rated insulation voltage [Ui]1000 V AC 50/60 Hz
Rated impulse withstand voltage [Uimp]12 kV
Poles description4P

Protection & Performance

LV848187 — Protection & Performance
ParameterValue
Rated service breaking capacity [Ics]66 kA at 220/415 V AC 50/60 Hz 66 kA at 440 V AC 50/60 Hz 66 kA at 500/525 V AC 50/60 Hz 66 kA at 660/690 V AC 50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Mechanical durability20000 cycles with periodic preventive maintenance
Electrical durabilityAC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3 2500 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 5000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23A: 2500 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 5000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3

Mechanical

LV848187 — Mechanical
ParameterValue
Connection pitch115 mm
Downside connectionFront Rear
Upside connectionFront Rear
Device short nameMTZ2 32 H1
Control typePush-button
Mounting modeFixed
Mounting supportRails Base plate
Width537 mm
Height352 mm
Depth300 mm

Environmental

LV848187 — Environmental
ParameterValue
IP degree of protectionIP30 conforming to EN 60529
Pollution degree3 conforming to IEC 60947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-40...85 °C

Approvals

LV848187 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12

Product details

The Schneider Electric LV848187 is a MasterPact MTZ2 32 H1 fixed-mount power circuit breaker rated 3200 A at 40 °C, with 4 poles and a Category B selectivity profile.

This breaker carries an H1 performance class: 66 kA Ics at 220/415 V, 440 V, 500/525 V, and 660/690 V AC. That's the service breaking capacity — the current it can clear and still be used again without inspection. The Icw short-time withstand is also 66 kA for 0.5, 1, and 3 seconds, which gives you real headroom for selective coordination downstream. Making capacity (Icm) hits 145 kA peak at 415 V, meaning it can close into a bolted fault and survive.

Physical fit and mounting constraints

Fixed-mount design, 537 mm wide, 352 mm tall, 300 mm deep. Connection pitch is 115 mm. Mounts on rails or a base plate. Neutral sits on the right. IP30 enclosure rating — it's for switchgear cubicles, not washdown areas.

Environmental and application limits

Rated insulation voltage is 1000 V AC, operational voltage 690 V AC. Impulse withstand is 12 kV — covers the typical surge environment in industrial power systems.

Durability and power loss

Mechanical endurance is 20,000 cycles with periodic preventive maintenance. Electrical durability varies by duty: 6,000 cycles under AC-3 (motor switching) at 440/690 V, 5,000 cycles under AC-23A at 440 V. Maximum break time is 25 ms, closing response 70 ms. Power dissipation runs 420 W at rated current — factor that into your cubicle ventilation.

Standards compliance and documentation

Meets EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H (for selectivity), and IEC 61557-12 (for power metering if equipped). Control is push-button type; this variant ships without a control unit — you add the Micrologic trip unit separately.

Frequently asked questions

Where can I buy LV848187 and how is it quoted?

The LV848187 is sourced and quoted to order through independent distribution channels. Availability and current pricing are confirmed at quote time against an RFQ — no runaround, just a straight answer on what it'll cost out of my pocket.

What are the key breaking capacities for LV848187?

Service breaking capacity (Ics) is 66 kA at 220/415 V, 440 V, 500/525 V, and 660/690 V AC. Short-time withstand (Icw) is also 66 kA for 0.5, 1, and 3 seconds. Making capacity (Icm) is 145 kA peak at 415 V. That's H1 performance class.

What is the closest alternative to LV848187 in the MasterPact family?

Within the MasterPact MTZ2 family, the closest alternative would be a different H-frame variant — for example, a 3200 A 3-pole instead of 4-pole, or a different performance class (H2 or) if you need higher Ics. The physical footprint and connection pitch are the same across MTZ2 fixed-mount units, so swapping performance class doesn't change your panel layout.

MPN