Skip to main content
Schneider Electric LV848815 — Circuit Breaker Accessories

LV848815 MicroLogic 3.0 X, MasterPacT, 690 V AC, LI protecti

MPNLV848815
Active

Schneider Electric MasterPacT MicroLogic 3.0 X control unit, LV848815, LI protection, LCD display, 690 V AC, 50/60 Hz.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LV848815 — Identification
ParameterValue
Product / component typeControl unit
Product rangeMasterPacT
Device applicationEquipment protection, monitoring and control
LV848815 — Electrical
ParameterValue
Network type (AC/DC)AC
Rated operational voltage [Ue]690 V AC, +/- 10 %
Network frequency50/60 Hz
LV848815 — Protection & Performance
ParameterValue
Trip unit technologyElectronic
Trip unit rating3600 A 400 A 4000 A 1000 A 1200 A 800 A 600 A 2500 A 1600 A 5000 A 3200 A 3000 A 2000 A 6000 A
Protection typeInstantaneous short-circuit protection conforming to ANSI 50 Overload (long time) conforming to ANSI 49
LV848815 — Mechanical
ParameterValue
Device short nameMicroLogic 3.0 X
LV848815 — Environmental
ParameterValue
Pollution degree3 conforming to IEC 60947-1
Operating ambient air temperature-25...70 °C (operating) -35 °C (for start-up of product)
LV848815 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60255-1 EN/IEC 60092-202 EN/IEC 60947-1

Product details

The Schneider Electric LV848815 is a MicroLogic 3.0 X electronic control unit for MasterPacT circuit breakers. It provides LI protection (long-time and instantaneous short-circuit) per ANSI 49 and 50, plus integrated power metering with a 128 x 96 pixel LCD display. Rated operational voltage is 690 V AC, with measurement voltage from 145.6 to 828 V AC per phase at 50/60 Hz. The unit supports 4P and 3P configurations, including 4P 3d + OSN and 4P 4d neutral protection settings.

Metering and accuracy

The control unit measures average voltage, power factor, frequency, RMS voltage, current (Ia, Ib, Ic, In, Ig), active/reactive/apparent power, and total harmonic distortion (THD) for both voltage and current. Accuracy classes include Class 0.5 for voltage unbalance, Class 1 for active/reactive energy, and Class 2 for voltage THD. Measurement accuracy for current is ±0.5 % over the 40–1600 A range (MTZ1 frame), ±0.5 % for 40–4000 A (MTZ2), and ±0.5 % for 80–6300 A (MTZ3). Active energy accuracy is ±1 % over 10 GWh; reactive energy ±2 % over 10 GVARh.

Protection and diagnostics

The LI protection curve offers adjustable long-time pickup (Ir) from 0.4 to 1 x In in 1 A steps, with long-time delay adjustable from 12.5 to 600 s at 1.5 x Ir. Instantaneous pickup (Ii) is adjustable. Thermal memory is included, and the unit logs alarms, events, and min/max values. Diagnostic features include circuit breaker health state, tripping cause indication, contact state, and MicroLogic service life tracking. The unit supports Bluetooth 4.0 LE, NFC, and USB communication for local configuration and data retrieval.

EMC compliance includes electrostatic discharge, electromagnetic field, fast transient/burst, surge (1.2/50 µs), and conducted RF immunity per IEC 61000-4-2 through -6. Conducted and radiated emissions meet Class A of CISPR 22.

Frequently asked questions

Where can I buy LV848815 and how do I get a price?

The LV848815 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key specifications of LV848815?

The LV848815 is a MicroLogic 3.0 X control unit for MasterPacT breakers, rated 690 V AC, 50/60 Hz, with LI protection, LCD display, and comprehensive power metering.

What compliance documentation does LV848815 have?

The unit complies with EN/IEC 60947-2, EN/IEC 60255-1, EN/IEC 60092-202 (marine), and EN/IEC 60947-1. EMC compliance per IEC 61000-4-2 through -6 and CISPR 22 Class A.

MPN
LV848815