Skip to main content
Schneider Electric LX0FK011 — Contactor & Starter Coils

Schneider TeSys F LX0FK011 Contactor Coil, 415 V AC

MPNLX0FK011
Active

Schneider Electric TeSys F contactor coil, LX0FK011, 415 V AC 50/60 Hz control circuit, latching resistance 112.06 Ohm at 20°C, 1 Mcycles mechanical durability.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX0FK011 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX0FK

Electrical

LX0FK011 — Electrical
ParameterValue
Control circuit voltage [Uc]415 V AC 50/60 Hz
Control circuit typeAC 50/60 Hz
Control circuit voltage limitsLatching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc
Coil resistance (avg.)112.06 Ohm latching 68 °F (20 °C) 13256 Ohm unlatching 68 °F (20 °C)

Performance & Durability

LX0FK011 — Performance & Durability
ParameterValue
Operating time50...100 ms unlatching 40...80 ms latching
Max. operating rate120 cyc/h 104 °F (40 °C)
Mechanical durability1 Mcycles

Product details

The LX0FK011 is a replacement contactor coil from the TeSys F range, designed to drive the main contactor in a motor starter or switching assembly. It operates on a 415 V AC 50/60 Hz control circuit, with the latching coil drawing 112.06 Ohm and the unlatching coil measuring 13256 Ohm at 68 °F (20 °C). This is a service part — category 18401-WORLD SERVICE PARTS(CTR ACCESS) — meaning it is stocked as a critical spare for installed TeSys F contactors. If you have a TeSys F contactor with a failed coil, this is the direct drop-in replacement.

The control circuit voltage is 415 V AC 50/60 Hz, with voltage limits of 0.85 to 1.1 Uc for both latching and unlatching. That means the coil will reliably pick up and drop out between roughly 353 V and 457 V — important when sourcing from a line that may sag under load. Operating time is 50 to 100 ms unlatching and 40 to 80 ms latching. For a contactor coil, this is standard — the unlatching time is the dropout delay, which governs how fast the main contacts open on a control signal loss. If your safety circuit timing relies on a faster dropout, verify this window against your requirements. At 120 cyc/h, that is one operation every 30 seconds — adequate for most motor starting duty, but not for high-speed jogging or rapid cycling applications.

Frequently asked questions

What contactor does this coil fit?

It is a service part for the TeSys F range of contactors. It is the direct replacement coil for any TeSys F contactor that uses a 415 V AC 50/60 Hz control circuit.

What are the control voltage limits for this coil?

The control circuit voltage limits are 0.85 to 1.1 Uc for both latching and unlatching. At the nominal 415 V AC, that means reliable operation between approximately 353 V and 457 V.

How fast does this coil operate?

Unlatching time is 50 to 100 ms; latching time is 40 to 80 ms. The maximum operating rate is 120 cycles per hour at 104 °F (40 °C).

MPN
LX0FK011