LX1D2FE7 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1D2
Coil technologyWithout built-in suppressor module
LX1D2FE7 — Electrical
ParameterValue
Control circuit voltage [Uc]115 V AC 50/60 Hz
Control circuit typeAC at 50/60 Hz
Control circuit voltage limitsOperational: 0.8...1.1 Uc at 50/60 Hz (at <55 °C)
LX1D2FE7 — Power & Thermal
ParameterValue
Inrush power (VA)70 VA 50/60 Hz cos phi 0.75 (at 20 °C)
Hold-in power (VA)8 VA 50/60 Hz cos phi 0.3 (at 20 °C)

Product details

The LX1D2FE7 is a replacement coil for TeSys D contactors in the 9–18 A frame — the LX1D2 variant. It pulls 70 VA inrush at 50/60 Hz (cos φ 0.75) and holds at 8 VA (cos φ 0.3), both at 20 °C. Coil voltage is 115 V AC 50/60 Hz, with an operating band of 0.8 to 1.1 Uc below 55 °C. No built-in suppressor module, so you'll want an external RC snubber or varistor across the coil if the PLC output driving it is solid-state.

This coil is marked obsolete by Schneider Electric. If you're kitting a spare for an existing panel, confirm the coil footprint and mounting match the LX1D2 armature before committing; the 115 V AC variant is common enough that a cross-reference exists in the aftermarket, but there's no single direct-replacement part number from Schneider.

Mounts directly onto the TeSys D contactor magnet assembly — no DIN-rail space consumed beyond the contactor itself. The coil terminals accept the same quick-connect tabs as the contactor coil socket. If you're swapping a failed coil in a live panel, kill the control transformer first; the 70 VA inrush can weld a relay contact if the supply is hot-dropped.

Frequently asked questions

What is the closest alternative to LX1D2FE7 in the TeSys D family?

There is no official direct-replacement order code from Schneider. The closest functional match is another LX1D2-series coil at 115 V AC, but you would need to verify the suppressor module and physical fit — the obsolete LX1D2FE7 lacks a built-in suppressor, so a replacement with one may change the control-circuit behavior.

What is the coil voltage and power draw?

Rated 115 V AC 50/60 Hz. Inrush power is 70 VA at cos φ 0.75; hold-in power is 8 VA at cos φ 0.3, both at 20 °C.

MPN