Schneider Electric LX1D2P5 — Contactor & Starter Coils

Schneider LX1D2P5 TeSys D Contactor Coil, 230 V AC 50 Hz, Ob

MPNLX1D2P5
Obsolete

Schneider Electric TeSys D, LX1D2P5 contactor coil, 230 V AC 50 Hz, for 9 to 18 A contactors.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX1D2P5 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1D2
Coil technologyWithout built-in suppressor module
LX1D2P5 — Electrical
ParameterValue
Control circuit voltage [Uc]230 V AC 50 Hz
Control circuit typeAC 50 Hz
Control circuit voltage limitsOperational: 0.8...1.1 Uc at 50 Hz (at <131 °F (55 °C))
Coil resistance (avg.)649.7 Ohm 68 °F (20 °C)
Coil inductance (closed circuit)25 H
LX1D2P5 — Power & Thermal
ParameterValue
Inrush power (VA)60 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power (VA)7 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))

Product details

The Schneider Electric LX1D2P5 is a replacement contactor coil from the TeSys D range, part of the LX1D2 device family. It is designed for 230 V AC 50 Hz control circuits and mates with 9 to 18 A TeSys D contactors. The coil draws 60 VA inrush at 50 Hz (cos φ 0.75) and holds at 7 VA (cos φ 0.3), both measured at 68 °F (20 °C). The closed-circuit inductance is 25 H, and the average DC resistance is 649.7 Ω at the same temperature. Operational voltage limits are 0.8 to 1.1 Uc at 50 Hz, up to 131 °F (55 °C). The coil has no built-in suppressor module — an external RC snubber or varistor should be added across the coil terminals if driving from a PLC output or electronic controller.

What to verify before ordering

This coil is AC 50 Hz only — it will not hold in on a 60 Hz supply or DC control voltage. The 230 V rating is nominal; the 0.8 to 1.1 Uc operating range means it drops out below roughly 184 V and may overheat above 253 V. Because the coil lacks a built-in suppressor, any inductive kickback when de-energizing must be managed externally. A standard RC snubber (0.1 µF + 100 Ω) across the coil terminals protects nearby electronics and extends contactor life.

Frequently asked questions

What contactors does this coil fit?

The LX1D2P5 is a TeSys D replacement coil for 9 to 18 A contactors in the same range. It is part of the LX1D2 device family and uses a 230 V AC 50 Hz control circuit.

Does this coil include a built-in surge suppressor?

No. The LX1D2P5 is specified without a built-in suppressor module. An external RC snubber or varistor should be added across the coil when switching with electronic controls.

What is the operating voltage range for this coil?

The operational limits are 0.8 to 1.1 times the nominal control voltage (230 V AC) at 50 Hz, up to 131 °F (55 °C). That gives a working range of approximately 184 to 253 V AC.

MPN