Schneider Electric LX1D6GG5 — Contactor & Starter Coils

TeSys LX1D6GG5 Contactor Coil, 155 V AC 50 Hz, Obsolete

MPNLX1D6GG5
Obsolete

Schneider Electric TeSys Deca LX1D6GG5, contactor coil, 155 V AC 50 Hz, for 80..95 A contactor, 6...10 W heat dissipation, 10 Mcycles mechanical durability.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX1D6GG5 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1D6
Coil technologyWithout built-in suppressor module
LX1D6GG5 — Electrical
ParameterValue
Control circuit voltage [Uc]155 V AC 50 Hz
Control circuit typeAC 50 Hz
Control circuit voltage limitsDrop-out: 0.3...0.6 Uc at 50/60 Hz (at Operational: 0.8...1.1 Uc at 50 Hz (at Operational: 0.85...1.1 Uc at 60 Hz (at <131 °F (55 °C))
Coil resistance (avg.)63.01 Ohm 68 °F (20 °C)
LX1D6GG5 — Power & Thermal
ParameterValue
Inrush power (VA)200 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power (VA)20 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation6...10 W 50/60 Hz
LX1D6GG5 — Performance & Durability
ParameterValue
Max. operating rate3600 cyc/h 140 °F (60 °C)
Mechanical durability10 Mcycles
LX1D6GG5 — Environmental
ParameterValue
Operating temperature23...140 °F (-5...60 °C)

Product details

The LX1D6GG5 is a replacement contactor coil from the TeSys Deca range, wound for 155 V AC 50 Hz control circuits. It is designed to fit TeSys Deca contactors rated 80 through 95 A — the coil that pulls in and holds the main power contacts. The coil draws 200 VA inrush at 50 Hz (cos φ 0.75) and holds at 20 VA (cos φ 0.3). Heat dissipation runs 6 to 10 W at 50/60 Hz, so panel builders should account for that thermal load when grouping multiple contactors in a confined enclosure. The coil has no built-in suppressor module — if your application requires surge suppression, you will need to add an external RC snubber or varistor across the coil terminals.

Because there is no direct replacement from the manufacturer, a redesign or substitution review is the recommended long-term fix. If you need a drop-in coil for an existing panel, the surplus channel is your option; for new builds, plan to select a current-production coil from the TeSys range that matches your control voltage and contactor frame.

Control circuit voltage and operating limits

The control circuit is rated 155 V AC 50 Hz. The coil will pick up reliably between 0.8 and 1.1 Uc at 50 Hz (124 to 170.5 V) and will drop out between 0.3 and 0.6 Uc (46.5 to 93 V). At 60 Hz the pickup range shifts to 0.85 to 1.1 Uc (131.75 to 170.5 V). These limits apply at ambient temperatures up to 55 °C. The coil's average resistance is 63.01 Ω at 20 °C. The hold-in power consumption of 20 VA means the coil stays cool during continuous duty, but the 200 VA inrush spike should be factored into control transformer sizing if multiple coils pull in simultaneously.

Frequently asked questions

What contactor does this coil fit?

It is designed for TeSys Deca contactors in the 80 to 95 A frame size. The coil is the LX1D6 variant, specific to 155 V AC 50 Hz control voltage.

Does this coil include a built-in surge suppressor?

No. The coil is listed as 'without built-in suppressor module'. An external RC snubber or varistor must be added if surge suppression is required for the control circuit.

What is the heat dissipation of this coil?

6 to 10 W at 50/60 Hz. This is the thermal load the coil adds to the enclosure — relevant when calculating cabinet cooling or grouping multiple contactors.