Skip to main content
Schneider Electric LX1FF264 — Contactor & Starter Coils

TeSys LX1FF264 Contactor Coil, 264 V AC 50 Hz, Obsolete

MPNLX1FF264
Obsolete

TeSys F series, LX1FF264, contactor coil, 264 V AC 50 Hz, 50 Hz AC coil, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX1FF264 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1FF
Coil technologyWithout built-in suppressor module
LX1FF264 — Electrical
ParameterValue
Control circuit voltage [Uc]264 V AC 50 Hz
Control circuit typeAC 50 Hz
Control circuit voltage limitsDrop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))
Coil resistance (avg.)37.5 Ohm 68 °F (20 °C)
Coil inductance (closed circuit)4.92 H
LX1FF264 — Power & Thermal
ParameterValue
Inrush power (VA)550 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Hold-in power (VA)45 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation12...16 W 50 Hz
LX1FF264 — Performance & Durability
ParameterValue
Operating time23...35 ms closing 5...15 ms opening
Max. operating rate2400 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles
LX1FF264 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX1FF264 is a replacement coil for TeSys F contactors, wound for 264 V AC at 50 Hz. It is a bare coil — no built-in suppressor module, so you add your own RC snubber or varistor across the terminals if the application demands it. Coil resistance measures 37.5 Ohm at 68 °F (20 °C); inrush power hits 550 VA at 50 Hz (cos φ 0.3), dropping to 45 VA holding. That 12-to-1 inrush-to-hold ratio is typical for an AC coil — the control transformer feeding it needs to handle the pick-up surge without drooping below 0.85 Uc. Closing time spans 23 to 35 ms; opening is faster at 5 to 15 ms.

For a BOM that needs this exact 264 V AC 50 Hz coil, the procurement path is a last-time-buy or a verified cross-reference from the TeSys F family.

Integration notes

Heat dissipation runs 12 to 16 W at 50 Hz — enough to matter inside a sealed enclosure. The coil sits on the TeSys F contactor frame; verify the mechanical interlock and auxiliary contact stack clear the coil profile before panel assembly. Drop-out threshold is 0.35 to 0.55 Uc at 131 °F (55 °C); operational range is 0.85 to 1.1 Uc. If the control transformer is shared with other AC coils, sequence the pick-up to avoid a cumulative voltage sag that keeps this coil from sealing.

Frequently asked questions

What is the control voltage and frequency for this coil?

264 V AC at 50 Hz. It is a 50 Hz-only coil — do not apply 60 Hz without verifying the thermal and magnetic performance.

Does this coil include a built-in suppressor?

No. The coil is supplied without a built-in suppressor module. An external RC snubber or varistor should be added across the coil terminals if inductive-load switching requires it.

MPN
LX1FF264