Skip to main content
Schneider Electric LX1FG850 — Contactor & Starter Coils

TeSys LX1FG850 Contactor Coil, 1000 V AC 60 Hz, Obsolete

MPNLX1FG850
Active

TeSys F, contactor coil, LX1FG850, 1000 V AC 60 Hz, 18-24 W heat dissipation, 10 Mcycles mechanical durability.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX1FG850 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1FG
Coil technologyWithout built-in suppressor module
LX1FG850 — Electrical
ParameterValue
Control circuit voltage [Uc]1000 V AC 60 Hz
Control circuit typeAC 60 Hz
Control circuit voltage limitsDrop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))
Coil resistance (avg.)249 Ohm 68 °F (20 °C)
Coil inductance (closed circuit)36.6 H
LX1FG850 — Power & Thermal
ParameterValue
Inrush power (VA)970 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
Hold-in power (VA)66 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation18...24 W 60 Hz
LX1FG850 — Performance & Durability
ParameterValue
Operating time20...35 ms closing 7...15 ms opening
Max. operating rate2400 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles
LX1FG850 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX1FG850 is a TeSys F contactor coil — the solenoid that pulls in the main power contacts on a TeSys F contactor. It's rated for 1000 V AC 60 Hz control circuits, with an inrush of 970 VA at 60 Hz and a hold-in draw of 66 VA. Operating time runs 20 to 35 ms closing, 7 to 15 ms opening.

The 1000 V AC 60 Hz control voltage is specific — this isn't a 24 VDC or 120 V coil. It's built for high-voltage AC control schemes, common in older or heavy industrial installations. The 18 to 24 W heat dissipation at 60 Hz means the coil generates noticeable heat; panel ventilation or spacing from heat-sensitive components matters. Drop-out voltage range is 0.35 to 0.55 Uc, operational range 0.85 to 1.1 Uc at 55 °C — so it holds in reliably down to 850 V AC and drops out below 550 V AC. That's a wide hysteresis, which helps prevent chatter on a sagging line.

Integration notes

This coil is a direct replacement for the TeSys F contactor range. No built-in suppressor module — if your circuit needs flyback suppression (and it should on a 1000 V AC coil driving an inductive load), you'll add an external RC snubber or varistor across the coil terminals. The average resistance is 249 ohms at 20 °C, inductance of the closed circuit is 36.6 H — that's a high inductance, so the flyback voltage spike on de-energization is substantial. Suppression isn't optional if you're switching it with a PLC output or a solid-state relay.

Frequently asked questions

What is the closest alternative to the LX1FG850?

No official replacement has been published. For a TeSys F contactor coil at 1000 V AC 60 Hz, you would need to source the exact LX1FG850 through surplus or broker channels, or re-engineer the control circuit for a different coil voltage.

What is the operating temperature range for this coil?

The ambient air temperature for operation is -5 to 55 °C (23 to 131 °F).

Does this coil include a built-in suppressor module?

No. The coil technology is listed as without built-in suppressor module. External suppression is required for inductive load switching.