Skip to main content
Schneider Electric LX1FH0522 — Contactor & Starter Coils

TeSys LX1FH0522 Contactor Coil, 52 V AC 40-400 Hz

MPNLX1FH0522
Active

Schneider Electric TeSys LX1FH0522, contactor coil, 52 V AC 40-400 Hz, 8 W dissipation, without built-in suppressor module.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LX1FH0522 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1FH
Coil technologyWithout built-in suppressor module
LX1FH0522 — Electrical
ParameterValue
Control circuit voltage [Uc]52 V AC 40...400 Hz
Control circuit typeAC 40...400 Hz
Control circuit voltage limitsDrop-out 0.35...0.55 Uc 40...400 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C))
LX1FH0522 — Power & Thermal
ParameterValue
Heat dissipation8 W 40...400 Hz
LX1FH0522 — Performance & Durability
ParameterValue
Operating time100...170 ms opening 40...65 ms closing
Max. operating rate2400 cyc/h 131 °F (55 °C)
LX1FH0522 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX1FH0522 is a replacement contactor coil from the TeSys range, designed for LX1F contactors. It operates on 52 V AC at 40 to 400 Hz, drawing 8 W of heat dissipation. The coil has no built-in suppressor module, so you'll need to add external suppression (RC snubber or varistor) across the coil terminals if driving it from a PLC output or electronic controller — the lack of internal suppression means the coil's inductive kickback is unmanaged without it.

Control circuit voltage is 52 V AC, with a dropout threshold of 0.35 to 0.55 Uc (roughly 18 to 29 V) and a pickup range of 0.85 to 1.1 Uc (44 to 57 V) at 55 °C. That means the coil will reliably pull in above about 44 V and drop out below about 29 V — important if your control transformer sags under load or you're running a long cable run. Opening time is 100 to 170 ms, closing time 40 to 65 ms; the maximum operating rate is 2400 cycles per hour at 55 °C, which is fine for most motor starting and switching duty but not for high-speed cycling applications like rapid reversing.

Frequently asked questions

What is the control voltage and frequency range?

The coil is rated for 52 V AC at 40 to 400 Hz. It will not work on DC control circuits.

Does this coil have a built-in suppressor?

No. The coil technology is listed as 'without built-in suppressor module'. You must add an external RC snubber or varistor across the coil if switching it with an electronic output.

What are the opening and closing times?

Opening time is 100 to 170 ms; closing time is 40 to 65 ms. Maximum operating rate is 2400 cycles per hour at 55 °C.

MPN