Schneider Electric LX1FH10002 — Contactor & Starter Coils

TeSys LX1FH10002 Contactor Coil, 1000 V AC 40-400 Hz

MPNLX1FH10002
Active

TeSys F, contactor coil, LX1FH10002, 1000 V AC 40...400 Hz, 650 VA inrush, 10 VA holding, without built-in suppressor module.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LX1FH10002 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1FH
Coil technologyWithout built-in suppressor module
LX1FH10002 — Electrical
ParameterValue
Control circuit voltage [Uc]1000 V AC 40...400 Hz
Control circuit typeAC 40...400 Hz
Control circuit voltage limitsDrop-out 0.35...0.55 Uc 40...400 Hz 131 °F (55 °C)) Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C))
Coil resistance (avg.)696 Ohm inrush 68 °F (20 °C) 25880 Ohm holding 68 °F (20 °C)
LX1FH10002 — Power & Thermal
ParameterValue
Inrush power (VA)650 VA 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))
Hold-in power (VA)10 VA 40...400 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation8 W 40...400 Hz
LX1FH10002 — Performance & Durability
ParameterValue
Operating time100...170 ms closing 40...65 ms opening
Max. operating rate2400 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles
LX1FH10002 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

Coil for TeSys F contactors — 1000 V AC control

The LX1FH10002 is a replacement coil for TeSys F contactors, rated for a 1000 V AC control circuit at 40...400 Hz. It draws 650 VA inrush (cos φ 0.9 at 20 °C) and settles to 10 VA holding (cos φ 0.3). No built-in suppressor module — plan external RC snubber or varistor across the coil if driving from a PLC or solid-state output, or the switching transient may couple noise into the control wiring.

Timing and duty cycle

Closing time spans 100...170 ms; opening takes 40...65 ms. Drop-out threshold is 0.35...0.55 Uc; pick-up requires 0.85...1.1 Uc at 55 °C. If your control supply sags under load, the coil may chatter before fully dropping out — check your transformer sizing against the 650 VA inrush peak.

Thermal and sourcing

Confirm the mating contactor frame (TeSys F) and the coil voltage before committing the BOM line — this is the 1000 V AC variant, not the more common 110...480 V coils in the same LX1FH family.

Frequently asked questions

What is the control voltage and frequency range?

1000 V AC, 40...400 Hz. Inrush is 650 VA at 20 °C; holding power drops to 10 VA.

Does this coil include a built-in suppressor?

No — the coil technology is listed as 'without built-in suppressor module'. An external RC snubber or varistor is recommended when switching with solid-state outputs.

What are the operating time and mechanical life?

Closing: 100...170 ms. Opening: 40...65 ms. Mechanical durability: 10 Mcycles. Maximum operating rate: 2400 cycles/hour at 55 °C.

MPN
LX1FH10002