The LX1FH11062 is a TeSys-series contactor coil — a replacement or spare coil for TeSys F contactors that take a 100 V AC 50 Hz or 100-110 V AC 60 Hz control voltage. It is rated for continuous duty and dissipates 8 W across the 40-400 Hz range, which is the heat the contactor's enclosure must shed. The coil has no built-in suppressor module, so if your circuit requires one (for example, to reduce switching transients on a PLC output), you add an external RC snubber or varistor across the coil terminals.
Voltage tolerance and timing
The coil picks up between 85% and 110% of rated control voltage (Uc) at 55 °C, and drops out between 35% and 55% of Uc. That means on a nominal 100 V AC supply, the contactor stays closed down to about 85 V and releases somewhere between 35 V and 55 V — a wide dropout band that accommodates brownout conditions without nuisance drop-out. Opening time is 100-170 ms; closing time is 40-65 ms. Maximum operating rate is 2400 cycles per hour at 55 °C, which is about 40 operations per minute — fine for most motor starting or resistive load switching, but not for high-speed jogging or rapid cycling.