Skip to main content
Schneider Electric LX1FK280 — Contactor & Starter Coils

TeSys LX1FK280 Contactor Coil, 265-277 VAC, Obsolete

MPNLX1FK280
Obsolete

TeSys F, contactor coil, LX1FK280, 265...277 V AC 40...400 Hz, 1100 VA inrush, 18 VA hold.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX1FK280 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1FK
Coil technologyWithout built-in suppressor module

Electrical

LX1FK280 — Electrical
ParameterValue
Control circuit voltage [Uc]265...277 V AC 40...400 Hz
Control circuit typeAC 40...400 Hz
Control circuit voltage limitsOperational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 40...400 Hz 131 °F (55 °C))
Coil resistance (avg.)56.5 Ohm inrush 68 °F (20 °C) 1490 Ohm holding 68 °F (20 °C)
Coil inductance (closed circuit)7.3 H

Power & Thermal

LX1FK280 — Power & Thermal
ParameterValue
Inrush power (VA)1100 VA 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))
Hold-in power (VA)18 VA 40...400 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation18 W 40...400 Hz

Performance & Durability

LX1FK280 — Performance & Durability
ParameterValue
Operating time100...170 ms opening 40...75 ms closing
Max. operating rate2400 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles

Environmental

LX1FK280 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

What this coil is

The LX1FK280 is a TeSys F contactor coil — a replacement coil for the TeSys F contactor range, designed to be swapped into the contactor frame. It operates on a 265...277 V AC control circuit at 40...400 Hz. This coil draws 1100 VA inrush at 68 °F (20 °C) and settles to 18 VA holding power. The inrush resistance is 56.5 Ω; the holding resistance is 1490 Ω. Heat dissipation runs 18 W across the 40...400 Hz range. Opening time is 100...170 ms; closing time is 40...75 ms.

Sourcing reality — obsolete

Verify the control voltage and mounting footprint against the existing contactor frame before committing.

Coil voltage and control circuit notes

The control circuit is AC only, 40...400 Hz. Operational voltage range is 0.85...1.1 Uc at 131 °F (55 °C). Drop-out occurs at 0.3...0.5 Uc. This coil has no built-in suppressor module. If the contactor frame or panel design expects a built-in varistor or RC snubber, an external suppressor must be added across the coil terminals to protect the control circuit from switching transients. The closed-circuit inductance is 7.3 H, which matters for sizing external suppression components — a higher inductance slows current decay and increases the voltage spike on opening.

Ambient operating temperature range is 23...131 °F (-5...55 °C). The coil mounts into the TeSys F contactor frame — no DIN-rail or panel footprint of its own; it is a drop-in replacement part for the contactor assembly.

Frequently asked questions

Does this coil include a built-in suppressor?

No. The LX1FK280 is supplied without a built-in suppressor module. An external RC snubber or varistor must be added across the coil if the application requires transient suppression.

MPN