Skip to main content
Schneider Electric LX1FK280

TeSys LX1FK280 Contactor Coil, 265-277 VAC, Obsolete

MPN LX1FK280
Obsolete

TeSys F, contactor coil, LX1FK280, 265...277 V AC 40...400 Hz, 1100 VA inrush, 18 VA hold.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LX1FK280 specifications
ParameterValue
Control circuit typeAC 40...400 Hz
Main product or component typeContactor coil
Coil voltage265...277 V AC 40...400 Hz
Temp operating max55 °C
Temp operating min-5 °C
Mechanical life cycles10 Mcycles
Operating time100...170 ms opening 40...75 ms closing
Operating temperature23...131 °F (-5...55 °C)

Product details

What this coil is

The LX1FK280 is a TeSys F contactor coil — a replacement coil for the TeSys F contactor range, designed to be swapped into the contactor frame. It operates on a 265...277 V AC control circuit at 40...400 Hz. This coil draws 1100 VA inrush at 68 °F (20 °C) and settles to 18 VA holding power. The inrush resistance is 56.5 Ω; the holding resistance is 1490 Ω. Heat dissipation runs 18 W across the 40...400 Hz range. Opening time is 100...170 ms; closing time is 40...75 ms.

Sourcing reality — obsolete

Verify the control voltage and mounting footprint against the existing contactor frame before committing.

Coil voltage and control circuit notes

The control circuit is AC only, 40...400 Hz. Operational voltage range is 0.85...1.1 Uc at 131 °F (55 °C). Drop-out occurs at 0.3...0.5 Uc. This coil has no built-in suppressor module. If the contactor frame or panel design expects a built-in varistor or RC snubber, an external suppressor must be added across the coil terminals to protect the control circuit from switching transients. The closed-circuit inductance is 7.3 H, which matters for sizing external suppression components — a higher inductance slows current decay and increases the voltage spike on opening.

Ambient operating temperature range is 23...131 °F (-5...55 °C). The coil mounts into the TeSys F contactor frame — no DIN-rail or panel footprint of its own; it is a drop-in replacement part for the contactor assembly.

MPN
LX1FK280