Skip to main content
Schneider Electric LX1FK350 — Contactor & Starter Coils

Schneider LX1FK350 TeSys Contactor Coil, 350 V AC

MPNLX1FK350
Obsolete

Schneider Electric TeSys LX1F series, LX1FK350, contactor coil, 350 V AC 50/60 Hz, without built-in suppressor module.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX1FK350 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1FK
Coil technologyWithout built-in suppressor module
LX1FK350 — Electrical
ParameterValue
Control circuit voltage [Uc]350 V AC 50/60 Hz
Control circuit typeAC 50/60 Hz
Control circuit voltage limitsOperational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 50/60 Hz 131 °F (55 °C))
Coil resistance (avg.)89.6 Ohm inrush 68 °F (20 °C) 2410 Ohm holding 68 °F (20 °C)
LX1FK350 — Performance & Durability
ParameterValue
Operating time100...170 ms opening 40...75 ms closing
Max. operating rate2400 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles
LX1FK350 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX1FK350 is a replacement coil for Schneider TeSys LX1F contactors, rated 350 V AC 50/60 Hz. It's the part that pulls the contactor in — no built-in suppressor module, so you supply your own RC snubber or varistor across the coil terminals if the application needs one. Coil resistance tells you the draw: 89.6 Ω inrush at 68 °F (20 °C) drops to 2410 Ω holding at the same temperature. That inrush-to-hold ratio is typical for AC-operated contactor coils — the high initial current slams the armature home, then the holding current drops to a fraction of that. Operating window is 100...170 ms opening, 40...75 ms closing. That's the mechanical travel time; add the control system's scan or relay delay when timing a safety circuit.

Voltage tolerance and dropout behaviour

Control circuit voltage limits are 0.85...1.1 Uc for operation at 131 °F (55 °C), meaning the coil must see between about 298 V and 385 V to pull in reliably. Dropout happens between 0.3 and 0.5 Uc — roughly 105 V to 175 V — so the contactor drops out cleanly on a brownout without chattering.

Listed as Active by Schneider. This is a current-production coil, not a last-time-buy or NRND part.

Durability and rate limits

Rated for 10 Mcycles mechanical — that's the coil and contactor mechanism together, not just the coil. Maximum operating rate is 2400 cycles per hour at 131 °F (55 °C), which works out to one operation every 1.5 seconds. Keep the ambient within -5...55 °C for rated life.

Frequently asked questions

What is the closest alternative to LX1FK350 in the TeSys family?

The LX1FK350 is a 350 V AC coil. Within the same LX1F family, other voltage variants exist (e.g., 110 V, 220 V, 400 V AC). The mechanical footprint and mounting are identical — the difference is the coil voltage. No pin-compatible alternative at the same voltage is listed; the 350 V AC variant is specific.

What is the TeSys range for this coil?

The LX1FK350 belongs to the Schneider TeSys range, specifically the LX1F series of contactor coils. It is a replacement coil for LX1F contactors.

What is the category of LX1FK350?

The category is 22341-CONTACTOR,D,K,&F ACCESS, which covers contactor accessories for TeSys D, K, and F ranges.

MPN