Schneider Electric LX1FX048 — Contactor & Starter Coils

Schneider TeSys LX1FX048 Contactor Coil, 48 V AC 50/60 Hz

MPNLX1FX048
Active

Schneider Electric TeSys LX1FX048, 48 V AC 50/60 Hz contactor coil, without built-in suppressor module, 5 Mcycles mechanical durability.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX1FX048 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1FX
Coil technologyWithout built-in suppressor module

Electrical

LX1FX048 — Electrical
ParameterValue
Control circuit voltage [Uc]48 V AC 50/60 Hz
Control circuit typeAC 50/60 Hz

Performance & Durability

LX1FX048 — Performance & Durability
ParameterValue
Max. operating rate600 cyc/h 131 °F (55 °C)
Mechanical durability5 Mcycles

Product details

The LX1FX048 is a replacement coil for Schneider TeSys F-size contactors, wound for 48 V AC control at 50/60 Hz. That 48 V AC coil voltage is the single spec that decides whether this part matches your existing contactor base — if your panel runs 48 V AC control transformers, this coil drops straight in. The coil carries no built-in suppressor module, so you'll need to add an external RC snubber or varistor across the coil terminals if your PLC output card or relay drives inductive loads; omitting suppression can weld auxiliary contacts or damage the driver.

Durability and operating rate

Rated for 5 million mechanical cycles, which for a coil in a contactor means the armature and return spring are good for the life of most conveyor or pump panels. The maximum operating rate is 600 cycles per hour at 55 °C — that's about 10 operations per minute, enough for frequent start-stop duty on a compressor or fan, but not for high-speed pick-and-place or servo indexing. If your application cycles faster than that, the coil temperature rise will exceed the insulation class; you'd need a larger contactor frame or a reduced-duty cycle.

Frequently asked questions

What is LX1FX048's listed range (TeSys) on this component line?

It belongs to the TeSys range, Schneider's modular contactor and motor-protection family. The device short name is LX1FX.

What is LX1FX048's listed category?

The category is 22341 — Contactor, D, K, & F Access. This groups it with replacement coils and accessory parts for TeSys D, K, and F frame contactors.

Does LX1FX048 include a built-in suppressor module?

No, the coil technology is listed as without built-in suppressor module. An external RC snubber or varistor should be added across the coil terminals when driven by electronic outputs.

MPN
LX1FX048