Skip to main content
Schneider Electric LX4FK065 — Contactor & Starter Coils

TeSys LX4FK065 Contactor Coil, 125 V DC, Active

MPNLX4FK065
Active

Schneider Electric TeSys F LX4FK065, contactor coil, 125 V DC, 45...60 ms opening, 50...60 ms closing, without built-in suppressor module.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX4FK065 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX4FK
Coil technologyWithout built-in suppressor module

Electrical

LX4FK065 — Electrical
ParameterValue
Control circuit voltage [Uc]125 V DC
Control circuit typeDC standard
Control circuit voltage limitsDrop-out 0.2...0.35 Uc 131 °F (55 °C)) Operational 0.85...1.1 Uc 131 °F (55 °C))
Coil resistance (avg.)3.73 Ohm inrush 68 °F (20 °C) 916 Ohm holding 68 °F (20 °C)
Coil inductance (closed circuit)122 H

Power & Thermal

LX4FK065 — Power & Thermal
ParameterValue
Inrush power (W)2100 W 68 °F (20 °C))
Hold-in power (W)10 W 68 °F (20 °C)

Performance & Durability

LX4FK065 — Performance & Durability
ParameterValue
Operating time45...60 ms opening 50...60 ms closing
Max. operating rate600 cyc/h 131 °F (55 °C)
Mechanical durability0.5 Mcycles

Environmental

LX4FK065 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX4FK065 is a replacement contactor coil from the Schneider Electric TeSys F range, designed for LX1FK contactors. It operates on a 125 V DC control circuit and is the service part you order when the original coil fails or a panel spec changes voltage.

Key electrical characteristics

The coil pulls in at 2100 W inrush at 20 °C, then holds at 10 W — the inrush resistance is 3.73 Ohm, holding resistance 916 Ohm. That wide ratio means the DC supply must deliver the inrush peak without droop; a marginal power supply can cause chatter on pickup. Control voltage limits are 0.85...1.1 Uc for operation and 0.2...0.35 Uc for drop-out at 55 °C. So at 125 V DC nominal, the coil drops out between 25 V and 44 V — useful to know if you have a long DC run with voltage drop. The closed-circuit inductance is 122 H, which combined with the holding resistance gives the low holding power. No built-in suppressor module is included, so you need an external flyback diode or RC snubber across the coil to protect the DC control circuit from the inductive kick.

Mechanical and thermal limits

The ambient temperature range for operation is -5 to 55 °C. These are the limits that govern replacement intervals in high-cycle applications like packaging or conveyor sortation. Opening time is 45...60 ms, closing time 50...60 ms. That timing matters when coordinating with upstream protection or sequencing multiple contactors in a motor control center.

Frequently asked questions

What is the closest pin-compatible alternative to LX4FK065 in this component family?

The LX4FK065 is the 125 V DC coil variant in the TeSys F LX1FK contactor family. Other voltage variants exist (e.g., 24 V DC, 48 V DC, 110 V DC, 220 V DC) but they are not pin-compatible substitutes — the coil voltage must match the control circuit. There is no single drop-in alternative; select the variant with the same control voltage.

What is LX4FK065's listed range on this component line?

The range is TeSys F, Schneider Electric's heavy-duty contactor series for motor switching and power distribution.

What is LX4FK065's listed category?

The category is 18401-WORLD SERVICE PARTS(CTR ACCESS), which is Schneider's internal classification for contactor accessory service parts available globally.

MPN
LX4FK065