Skip to main content
Schneider Electric LX4FK090 — Contactor & Starter Coils

TeSys LX4FK090 contactor coil, 90 V DC, active

MPNLX4FK090
Active

Schneider Electric TeSys LX4FK090 contactor coil, 90 V DC, FK series, active lifecycle.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX4FK090 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX4FK
Coil technologyWithout built-in suppressor module

Electrical

LX4FK090 — Electrical
ParameterValue
Control circuit voltage [Uc]90 V DC
Control circuit typeDC low consumption
Control circuit voltage limitsDrop-out 0.2...0.35 Uc 131 °F (55 °C)) Operational 0.85...1.1 Uc 131 °F (55 °C))
Coil resistance (avg.)1917 Ohm holding 68 °F (20 °C) 7.47 Ohm inrush 68 °F (20 °C)

Performance & Durability

LX4FK090 — Performance & Durability
ParameterValue
Operating time45...60 ms opening 50...60 ms closing

Environmental

LX4FK090 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX4FK090 is a replacement contactor coil for the TeSys FK series — a DC low-consumption coil pulling in at 90 V DC nominal. It's the part you swap when the coil on a FK contactor opens or the control voltage drops out; no built-in suppressor module, so plan for an external flyback diode or RC snubber across the coil terminals if your PLC output or relay can't handle the inductive kick.

Operating time runs 45 to 60 ms on opening and 50 to 60 ms on closing — that's standard for a DC coil this size, but if your safety circuit demands faster break, this won't meet a sub-30 ms window. The holding resistance sits at 1917 ohms at 20 °C, with an inrush resistance of 7.47 ohms at the same temperature; that inrush-to-hold ratio means the coil draws a healthy surge on pickup, so size your 90 V DC supply to handle the momentary load without dropping below the 0.85 Uc operational limit. Drop-out threshold is 0.2 to 0.35 Uc at 55 °C — roughly 18 to 31.5 V DC — so the contactor stays in during a brownout down to about a third of nominal.

Frequently asked questions

What is LX4FK090's listed range (TeSys) on this component line?

It belongs to the TeSys range, which covers contactors, overload relays, and accessories for motor control.

What is LX4FK090's listed category (18401-WORLD SERVICE PARTS(CTR ACCESS)) on this component line?

The category is 18401 — WORLD SERVICE PARTS (CTR ACCESS), indicating it's a service-part accessory for contactors, not a primary device.

MPN
LX4FK090