Schneider Electric LX9FJ928 — Contactor & Starter Coils

TeSys LX9FJ928 Contactor Coil, 155 V AC / 140-156 V DC

MPNLX9FJ928
Active

Schneider Electric TeSys F series, specific contactor coil LX9FJ928, 155 V AC / 140-156 V DC, 60 ms opening, 20 ms closing.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX9FJ928 — Identification
ParameterValue
Product typeSpecific contactor coil
Product rangeTeSys
Device short nameLX9FJ
Coil technologyWithout built-in suppressor module

Electrical

LX9FJ928 — Electrical
ParameterValue
Control circuit voltage [Uc]140...156 V DC 155 V AC 40...400 Hz
Control circuit typeAC 40...400 Hz low consumption DC low consumption
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 131 °F (55 °C))

Power & Thermal

LX9FJ928 — Power & Thermal
ParameterValue
Inrush power (VA)500 VA 40...400 Hz (at 68 °F (20 °C))
Hold-in power (VA)23 VA 40...400 Hz (at 68 °F (20 °C))
Heat dissipation11.4...13.9 W

Performance & Durability

LX9FJ928 — Performance & Durability
ParameterValue
Operating time60 ms opening 20 ms closing
Max. operating rate3600 cyc/h 158 °F (70 °C)
Mechanical durability10 Mcycles

Environmental

LX9FJ928 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX9FJ928 is a specific replacement coil for the TeSys F contactor range, designed for environments where ambient temperature stays below 70 °C. It's the part you pull when a contactor coil fails open or shorted, not the whole contactor assembly — keeps the panel rebuild to a single component swap. Control voltage is dual-rated: 155 V AC at 40-400 Hz, or 140 to 156 V DC. That covers both legacy 110 VAC control schemes stepped up through a transformer and 125 VDC battery-backed trip circuits common in utility and industrial switchgear. Opening time is 60 ms, closing time 20 ms. For a coil swap, those numbers matter for coordination with upstream breaker trip curves — the 60 ms opening means the contactor clears before a molded-case breaker's short-time delay expires on a fault.

Installation note — suppressor module required

This coil ships without a built-in suppressor module. On AC control, that means you need to add an external RC snubber or varistor across the coil terminals to prevent back-EMF from welding auxiliary contacts or glitching the PLC output driving it. On DC control, a free-wheeling diode is mandatory — polarity-sensitive, so verify before wiring. Heat dissipation runs 11.4 to 13.9 W. In a densely packed panel, that's enough to raise the internal ambient a few degrees — check the TeSys F thermal derating curve if the enclosure is already near the 55 °C operating limit.

Frequently asked questions

What is LX9FJ928's listed range on this component line?

It belongs to the TeSys range, specifically the TeSys F series of contactors and accessories.

What control voltages does the LX9FJ928 coil accept?

It accepts 155 V AC at 40-400 Hz, or 140 to 156 V DC. The operational limits are 0.85 to 1.1 Uc at 55 °C, with dropout between 0.3 and 0.5 Uc.

Does the LX9FJ928 include a built-in surge suppressor?

No, it is listed as 'Without built-in suppressor module'. An external RC snubber (AC) or free-wheeling diode (DC) must be added to protect control circuit contacts.

MPN