Skip to main content
Schneider Electric LX9FK921 — Contactor & Starter Coils

Schneider TeSys LX9FK921 Contactor Coil 63-70 VDC

MPNLX9FK921
Active

Schneider Electric TeSys F, specific contactor coil, LX9FK921, 63..70 V DC, low consumption, 550 VA inrush.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX9FK921 — Identification
ParameterValue
Product typeSpecific contactor coil
Product rangeTeSys
Device short nameLX9FK
Coil technologyWithout built-in suppressor module

Electrical

LX9FK921 — Electrical
ParameterValue
Control circuit voltage [Uc]63...70 V DC
Control circuit typeAC 40...400 Hz low consumption DC low consumption
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 131 °F (55 °C))

Power & Thermal

LX9FK921 — Power & Thermal
ParameterValue
Inrush power (VA)550 VA (at 68 °F (20 °C))
Hold-in power (VA)31 VA (at 68 °F (20 °C))
Heat dissipation15...18.3 W

Performance & Durability

LX9FK921 — Performance & Durability
ParameterValue
Operating time60 ms opening 50 ms closing
Max. operating rate3600 cyc/h 158 °F (70 °C)
Mechanical durability10 Mcycles

Environmental

LX9FK921 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

Part identification and control voltage

The LX9FK921 is a specific contactor coil from the Schneider Electric TeSys range, designed for TeSys F contactors. It operates on a 63...70 V DC control circuit and is classified as low consumption. The coil draws an inrush power of 550 VA at 68 °F (20 °C) and a hold-in power consumption of 31 VA at the same temperature, with heat dissipation in the 15...18.3 W range during steady-state operation. This coil is supplied without a built-in suppressor module, so you will need to add external suppression if the control circuit demands it — standard practice for DC coils driving inductive loads.

Switching performance and durability

Opening time is 60 ms; closing time is 50 ms. These figures matter when sequencing contactors in a motor start circuit — the 10 ms asymmetry is typical for DC coils and must be accounted for in interlock timing. For high-duty applications like conveyor indexing or compressor cycling, this rate sets the practical switching ceiling. The ambient air temperature range for operation is 23 to 131 °F (-5 to 55 °C). The control voltage limits are 0.85...1.1 Uc for operational range and dropout at 0.3...0.5 Uc, both at 131 °F (55 °C).

The active status removes the urgency of a last-time-buy window, but given its role as a specific contactor coil for the TeSys F platform, verifying compatibility with the specific contactor frame (LX9F body) is the only integration check needed.

Frequently asked questions

What is the control voltage for this coil?

The control circuit voltage is 63...70 V DC, with operational limits of 0.85 to 1.1 times Uc and dropout at 0.3 to 0.5 times Uc at 131 °F (55 °C).

Does this coil include a built-in suppressor?

No, it is supplied without a built-in suppressor module. External suppression must be added for inductive load control circuits.

What is the inrush and hold-in power consumption?

Inrush power is 550 VA at 68 °F (20 °C), and hold-in power consumption is 31 VA at the same temperature. Heat dissipation ranges from 15 to 18.3 W.

MPN
LX9FK921