Skip to main content
Schneider Electric LX9FK923 — Contactor & Starter Coils

TeSys LX9FK923 Specific Contactor Coil, 80..88 V DC, Low Con

MPNLX9FK923
Active

TeSys F specific contactor coil, LX9FK923, 80..88 V DC, low consumption, 60 ms opening / 50 ms closing, no built-in suppressor.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX9FK923 — Identification
ParameterValue
Product typeSpecific contactor coil
Product rangeTeSys
Device short nameLX9FK
Coil technologyWithout built-in suppressor module

Electrical

LX9FK923 — Electrical
ParameterValue
Control circuit voltage [Uc]80...88 V DC
Control circuit typeAC 40...400 Hz low consumption DC low consumption
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 131 °F (55 °C))

Power & Thermal

LX9FK923 — Power & Thermal
ParameterValue
Inrush power (VA)550 VA (at 68 °F (20 °C))
Hold-in power (VA)31 VA (at 68 °F (20 °C))
Heat dissipation15...18.3 W

Performance & Durability

LX9FK923 — Performance & Durability
ParameterValue
Operating time60 ms opening 50 ms closing
Max. operating rate3600 cyc/h 158 °F (70 °C)
Mechanical durability10 Mcycles

Environmental

LX9FK923 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX9FK923 is a specific contactor coil from the TeSys F range, designed as a replacement coil for TeSys F contactors. It operates on an 80...88 V DC control circuit and is classified as low consumption. This coil draws 550 VA inrush at 20 °C and holds at 31 VA, with heat dissipation between 15 and 18.3 W during continuous operation. The opening time is 60 ms and closing time is 50 ms, which matters when coordinating contactor timing in a motor starter or reversing circuit.

Coil voltage and control circuit

Rated for 80...88 V DC, the coil holds in from 0.85 to 1.1 Uc at 55 °C and drops out between 0.3 and 0.5 Uc. That dropout threshold is low — about 24 to 40 V — so the contactor stays pulled in during a sag, but will drop cleanly on a loss of control voltage. There is no built-in suppressor module, so you need to add an external flyback diode or RC snubber across the coil if the control circuit drives inductive loads like a PLC output or relay. Without it, the back-EMF from the coil can damage solid-state outputs.

Integration notes

Maximum operating rate is 3600 cycles per hour at 70 °C. The coil is AC and low-consumption DC compatible across 40 to 400 Hz — but note the DC voltage range is tight at 80...88 V. Verify your control transformer or DC supply stays within that band, especially under load.

Frequently asked questions

What is the control voltage range for the LX9FK923?

The coil is rated for 80...88 V DC. The operating limits are 0.85 to 1.1 Uc (68 to 97 V) at 55 °C, and dropout occurs between 0.3 and 0.5 Uc (24 to 44 V).

Does the LX9FK923 include a built-in surge suppressor?

No. The coil is listed as 'Without built-in suppressor module'. An external flyback diode or RC snubber must be added if the control circuit contains solid-state outputs or inductive loads.

What is the heat dissipation of this coil?

Between 15 and 18.3 W during continuous operation. That thermal load should be considered when sizing the enclosure ventilation or when multiple coils are mounted close together.

MPN