Skip to main content
Schneider Electric MGN25090 — 1-Pole MCB (DIN Rail)

MGN25090 C60H MCB, 1P D-curve 40 A, 15 kA breaking

MPNMGN25090
Obsolete

Schneider Electric Multi9 C60H series, MGN25090 miniature circuit breaker, 1-pole, D-curve, 40 A rated current, 15 kA breaking capacity at 240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN25090 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
MGN25090 — Electrical & Protection
ParameterValue
Rated current (In)40 A at 50 °C conforming to EN/IEC 60947-2
Rated operational voltage (Ue)240 V AC 50/60 Hz phase to neutral
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu / AIR)15 kA Icu at 240 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 4 kA Icu at 415 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGN25090 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals1.5...35 mm² flexible without cable end Tunnel type terminals1.5...35 mm² flexible with cable end Tunnel type terminals1.5...35 mm² rigid
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)Power circuit: 3.5 N.m
MGN25090 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
MGN25090 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2

Product details

The MGN25090 is a 1-pole C60H miniature circuit breaker from the Multi9 range, rated 40 A at 50 °C per EN/IEC 60947-2. The D-curve magnetic trip limit of 12 x In (±20 %) means it holds through motor inrush without nuisance tripping — sized for distribution or motor feeder circuits where the starting surge exceeds 8 x In. The 15 kA Icu at 240 V AC (phase-to-neutral) is the maximum fault current it can safely interrupt; the service breaking capacity Ics is 7.5 kA (50 %) at the same voltage, so for a 240 V panel with available fault current under 7.5 kA the breaker can be reclosed after a fault without replacement. The tunnel-type terminals accept 1.5 to 35 mm² rigid or flexible conductors; tighten to 3.5 N·m. IP20 finger-safe front, pollution degree 3 rated — suitable for standard control panels, not washdown environments.

The suitability-for-isolation marking (visible ON/OFF indication and contact position indicator) means it can serve as a disconnecting means per the standard — no separate isolator needed upstream in a 240 V single-phase feeder.

Frequently asked questions

Who supplies MGN25090 and how is it quoted for volume purchases?

The MGN25090 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is MGN25090's breaking capacity at 240 V AC?

The MGN25090 has a breaking capacity Icu of 15 kA at 240 V AC 50/60 Hz phase-to-neutral per EN/IEC 60947-2, with a service breaking capacity Ics of 7.5 kA (50 %) at the same voltage.

What compliance standards does MGN25090 meet?

The MGN25090 is designed and tested to EN/IEC 60947-2, utilisation category A, with pollution degree 3 and IP20 protection.

MPN
MGN25090