Skip to main content
Schneider Electric MGN25112

MGN25112 C60H MCB, 2P D-curve 3 A, 30 kA breaking capacity

MPN MGN25112
Obsolete

Schneider Electric C60H Multi9 miniature circuit breaker, MGN25112, 2-pole, D-curve, 3 A rated current, 30 kA breaking capacity at 240 V AC, thermal-magnetic trip, 35 mm DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN25112 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-30 °C
Storage temperature-40...80 °C
Pollution degree3 conforming to EN/IEC 60947-2

All specifications

MGN25112 additional specifications
ParameterValue
Depth73 mm
Width36 mm
Height81 mm
Electrical life cycles10000 cycles conforming to EN/IEC 60947-2
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-30...70 °C

Product details

The MGN25112 is a Schneider Electric C60H miniature circuit breaker from the Multi9 range — a 2-pole, D-curve unit rated 3 A, built for distribution duty in 35 mm DIN-rail enclosures. Breaking capacity hits 30 kA Icu at 240 V AC phase-to-phase (15 kA at 415 V, 10 kA at 440 V), which puts it in the C60H tier — high enough for most commercial and light-industrial panelboards where fault current runs under 30 kA.

The 3 A rating is at 50 °C per EN/IEC 60947-2, so no derating is needed at typical panel ambient; above that, the thermal-magnetic trip element adjusts naturally. Service breaking capacity (Ics) is 50 % of Icu — 15 kA at 240 V, 7.5 kA at 415 V, 5 kA at 440 V — meaning after clearing a fault at that level the breaker remains functional, not just safe.

Snaps onto 35 mm symmetrical DIN rail (EN/IEC 60947-2), occupies 4 x 9 mm pitches (36 mm wide) — two-pole width, standard for a 2P MCB in a Multi9 lineup. IP20 finger-safe front; pollution degree 3 per EN/IEC 60947-2, so it's rated for the conductive-dust environment inside a typical panel.