Skip to main content
Schneider Electric MGN61889 — 2-Pole MCB (DIN Rail)

MGN61889 Multi9 C60H-DC MCB, 40 A, 2P, K Curve, 20 kA DC

MPNMGN61889
Obsolete

Schneider Electric Multi9 C60H-DC, MGN61889, miniature circuit-breaker, 2P, 40 A, K curve, 20 kA Icu at 250 V DC, clip-on DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

MGN61889 — Identification
ParameterValue
Product nameMulti9 C60H-DC
Series / familyMulti9
Device short nameC60H-DC
Product / component typeMiniature circuit-breaker
Device applicationDistribution
MGN61889 — Electrical
ParameterValue
Rated current [In]40 A at 50 °C conforming to EN/IEC 60947-2
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]250 V DC 500 V DC 220 V DC 440 V DC
Network type (AC/DC)DC
MGN61889 — Protection
ParameterValue
Tripping curve codeK
Magnetic tripping limit12 x In +/- 20 % DC
Breaking capacity (Icu)20 kA Icu at 220 V DC conforming to EN/IEC 60947-2 20 kA Icu at 250 V DC conforming to EN/IEC 60947-2 10 kA Icu at 440 V DC conforming to EN/IEC 60947-2 6 kA Icu at 500 V DC conforming to EN/IEC 60947-2
Rated service breaking capacity [Ics]15 kA 75 % conforming to EN/IEC 60947-2 - 220 V DC 15 kA 75 % conforming to EN/IEC 60947-2 - 250 V DC 7.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V DC 4.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V
Suitable for isolationYes conforming to EN/IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
MGN61889 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81 mm
Depth73 mm
Mounting supportDIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminal (top or bottom)1...35 mm² (AWG 18...AWG 2) - rigid stranded Tunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - flexible Tunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - flexible with ferrule Tunnel type terminal (top or bottom) - 2 cable(s) 1...16 mm² (AWG 18...AWG 6) - rigid stranded Tunnel type terminal (top or bottom) - 2 cable(s) 1...16 mm² (AWG 18...AWG 6) - flexible Tunnel type terminal (top or bottom) - 2 cable(s) 1...16 mm² (AWG 18...AWG 6) - flexible with ferrule Tunnel type terminal (top or bottom) - 3 cable(s) 4 mm² (AWG 6) - flexible stranded
Terminal tightening torque3.5 N.m top or bottom
Local signalling / indicationON/OFF indication
Contact position indicatorYes
MGN61889 — Environmental
ParameterValue
Operating temperature range-25...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
MGN61889 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2

Product details

The Schneider Electric MGN61889 is a Multi9 C60H-DC miniature circuit-breaker for DC networks. It is a 2-pole, 40 A unit with a K trip curve, clips onto DIN rail, and occupies 4 modular pitches (36 mm wide, 81 mm tall, 73 mm deep). The thermal-magnetic trip unit handles the overload side; the magnetic element clears short-circuits. This is not a general-purpose AC breaker — it is rated and tested for DC only, with a utilisation category A per EN/IEC 60947-2. Breaking capacity is the key fit check: 20 kA Icu at 220 V DC and 250 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC. Rated insulation voltage (Ui) is 500 V DC, and the rated operational voltage (Ue) covers 220 V, 250 V, 440 V, and 500 V DC systems.

Mounts via clip-on to DIN rail. The terminals can also accept two or three conductors per pole — useful for daisy-chaining downstream loads without extra terminal blocks. IP20 on the terminals, IP40 on the modular enclosure — suitable for dry indoor panels. The toggle switch provides local ON/OFF indication, and the contact position indicator confirms isolation status (suitability for isolation is marked on the device). Padlockable for lockout/tagout.

Standards compliance: EN/IEC 60947-2. Tropicalisation per IEC 60068-2 (class 2) means it withstands humidity up to 95 % at 55 °C.

Frequently asked questions

What is the breaking capacity of the MGN61889 at 250 V DC?

20 kA Icu at 250 V DC per EN/IEC 60947-2. At 440 V DC it drops to 10 kA, and at 500 V DC to 6 kA. Verify your available fault current against these ratings before specifying.

What does the K curve mean on this DC MCB?

The K curve sets the magnetic trip threshold at 12 x In (±20 %). This is designed for DC circuits with high inrush currents — motor loads, solenoids, power supplies — where a B or C curve would trip on startup. The thermal element handles overloads; the magnetic element clears short-circuits.