Skip to main content
Schneider Electric MGP0801L2 — 1-Pole MCB (DIN Rail)

MGP0801L2 PowerPacT 4 1P 80A Circuit Breaker, Obsolete

MPNMGP0801L2
Obsolete

Schneider Electric PowerPacT 4, molded case circuit breaker, 1P, L2 phase, 80 A at 40 °C, 230 V AC, 25 kA Icu, panel-mounted, obsolete.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGP0801L2 — Identification
ParameterValue
Product / component typeCircuit breaker
Poles description1P
Device applicationDistribution
MGP0801L2 — Electrical & Protection
ParameterValue
Rated current (In)80 A at 40 °C
Rated operational voltage (Ue)230 V AC 50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGP0801L2 — Mounting & Connection
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical
MGP0801L2 — Approvals
ParameterValue
Conformity standardsBS EN 60947-2
MGP0801L2 — Electrical
ParameterValue
[Ui] rated insulation voltage750 V
[Uimp] rated impulse withstand voltage8 kV

Product details

The MGP0801L2 is a 1-pole molded case circuit breaker (MCCB) from the PowerPacT 4 range, rated 80 A at 40 °C with a TM-D thermal-magnetic trip unit providing LI protection — thermal overload (L) and magnetic short-circuit (I). It is designed for distribution applications and carries a 25 kA Icu and Ics at 230 V AC 50/60 Hz, with a rated insulation voltage of 750 V and impulse withstand of 8 kV. The toggle control type and backplate mounting suit panel-mounted distribution boards where a compact 1-module (35 mm) footprint is needed.

Lifecycle reality — obsolete, sourced through independent channels

This part is officially obsolete per the manufacturer's lifecycle status.

The thermal-magnetic LI trip responds to overload (thermal) and short-circuit (magnetic) currents; there is no earth-leakage protection built in. The Ics is equal at 25 kA, meaning it can also be reclosed after a fault at that level — useful for service-entrance or main-panel positions where fault current is high. The 750 V insulation rating and 8 kV impulse withstand cover it for most distribution panels. Electrical durability is 20,000 cycles at rated current, 10,000 cycles at In/2 — enough for a distribution breaker that cycles infrequently.

Conforms to BS EN 60947-2, the standard for low-voltage switchgear and controlgear. It is also suitable for isolation per that standard. Utilisation category A means it is not specifically intended for motor starting (category B would be for motor protection). Use it for cable and distribution protection.

Frequently asked questions

Where can I buy MGP0801L2?

It is sourced to order against an RFQ through independent distribution and surplus channels. Availability and current pricing are confirmed at quote time.

What are the key ratings of MGP0801L2?

80 A rated current at 40 °C, 230 V AC 50/60 Hz operational voltage, 25 kA Icu/Ics short-circuit breaking capacity, thermal-magnetic LI trip unit, 1-pole, panel-mounted.

What standard does MGP0801L2 comply with?

It conforms to BS EN 60947-2 and is suitable for isolation per that standard.

MPN
MGP0801L2