Schneider Electric VW3A46107A — AC Drive (VFD) 480V

Schneider VW3A46107A Passive Filter, 50 A, 380-480 V, 22 kW,

MPNVW3A46107A
Active

Schneider Electric Easy Altivar 610 passive filter, VW3A46107A, 50 A output, 380-480 V, 22 kW/30 hp, 50 Hz, THDI 10%, IP20.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

VW3A46107A — Identification
ParameterValue
Product typePassive filter

Input / Supply

VW3A46107A — Input / Supply
ParameterValue
Rated supply voltage range380...480 V +/- 10 %
Network number of phases3 phases

Mechanical & Cooling

VW3A46107A — Mechanical & Cooling
ParameterValue
IP degree of protectionIP20 (enclosure mounting)

Environmental

VW3A46107A — Environmental
ParameterValue
Operating ambient temperature-25...45 °C (without current derating)
Storage / transport temperature-25...85 °C storage in original packaging

Approvals

VW3A46107A — Approvals
ParameterValue
Standards complianceUL 61800-5-1 IEC 61800-5-1

Other specifications

VW3A46107A — Other specifications
ParameterValue
THDI10 % for variable speed drive ATV610
Efficiency98 %
Thermal losses327 W
Quantity per drive1 filter per drive for variable speed drive ATV610 motor: 22 kW/30 hp
Current32.5 A for input 50 A for output
Electrical connectionL1, L2, L3, L1', L2', L3' terminal, connection capacity: 0.5...10 mm² D1, D2, D3, D1', D2', D3' terminal, connection capacity: 2.5 mm² TS, TS' terminal, connection capacity: 0.5...4 mm²
Power supply frequency50 Hz +/- 2 %
Electrical insulation classClass N

Product details

Passive filter for ATV610 drives — 22 kW, 50 A output, THDI 10%

The VW3A46107A is a passive filter designed to pair with a Schneider ATV610 variable speed drive running a 22 kW / 30 hp motor on a 380-480 V three-phase line. It knocks input current harmonics down to 10 % THDI, which keeps the drive from rattling the rest of the panel's gear — especially important on shared transformers or generator-fed sites. The filter is rated for 32.5 A on the input side and 50 A on the output, so it handles the drive's full draw without choking. Efficiency sits at 98 %, with 327 W of thermal losses to vent. That's heat you need to account for in the enclosure — at full load it's about the same as a small space heater running inside the cabinet. Mounting is IP20, so it's meant for a clean, dry panel environment, not out in the washdown zone.

The 10 % THDI figure is what matters most here. Without a line filter, a standard VFD can push higher THDI back onto the line, tripping nuisance breakers or overheating transformers upstream. This filter brings that down to 10 %, which is clean enough to meet most plant power-quality specs without going to a full active front end. The UL 61800-5-1 and IEC 61800-5-1 certifications mean it's tested as part of a drive system for both safety and harmonic limits — not just a standalone choke. The 50 A output rating matches the drive's nominal current for a 22 kW motor at 400 V. The input rating of 32.5 A reflects the lower current draw on the line side after the filter's inductive stage. Connection terminals accept up to 10 mm² on the power lines and 2.5 mm² for the DC bus links — solid for the wire sizes you'd run on a 22 kW drive.

Frequently asked questions

What is VW3A46107A's listed THDI?

The VW3A46107A achieves 10 % THDI when used with an ATV610 variable speed drive.

What standards does VW3A46107A comply with?

It complies with UL 61800-5-1 and IEC 61800-5-1, covering safety and harmonic performance for adjustable-speed drive systems.

MPN
VW3A46107A