Skip to main content
Siemens 3VA1010-4ED32-0BC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-4ED32-0BC0 SENTRON MCCB, 100 A, 3-Pole, 121

MPN3VA1010-4ED32-0BC0

Siemens SENTRON 3VA1010-4ED32-0BC0, Molded case circuit breaker, 3-pole, 100 A, 121 kA at 240 V, line protection, TM210 release, undervoltage release, IP40 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1010-4ED32-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1010-4ED32-0BC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA
3VA1010-4ED32-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1010-4ED32-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-4ED32-0BC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1010-4ED32-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-4ED32-0BC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1010-4ED32-0BC0 is a 3-pole molded case circuit breaker rated for 100 A continuous current (Iu) across ambient temperatures up to 50 °C, with a thermal-magnetic TM210 release for line protection. Its interrupting capacity hits 121 kA at 240 V and 75.6 kA at 415 V — numbers that matter when you're coordinating downstream breakers in a distribution panel and need the main to hold fault current without letting it cascade upstream.

Thermal derating and real-world loading

Above that, it derates: 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C.

Auxiliaries and releases

Comes with an undervoltage release (UVR) built in — that's the '4ED' in the order code telling you it's there. The auxiliary trip accessory is order code 3VA9608-0BB11 if you need a shunt trip later.

Dimensions: 130 mm height, 76.2 mm width (3-pole), 70 mm depth. The IP40 front face means the breaker handle and nameplate are protected against solid objects over 1 mm, but the enclosure needs to handle the rest of the IP rating.

Frequently asked questions

Where can I buy 3VA1010-4ED32-0BC0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the interrupting capacity of 3VA1010-4ED32-0BC0 at 415 V?

75.6 kA at 415 V, with 121 kA at 240 V and 52.5 kA at 440 V.

What is the difference between 3VA1010-4ED32-0BC0 and 3VA1010-2ED32-0JA0?

The 3VA1010-2ED32-0JA0 is a functionally similar 3-pole 100 A MCCB but with a different auxiliary contact configuration and no undervoltage release. The 3VA1010-4ED32-0BC0 includes the UVR and two HQ auxiliary switches. Both share the same frame size and TM210 release, so they can swap in the same panel footprint, but the UVR wiring must be accounted for.

MPN
3VA1010-4ED32-0BC0