Skip to main content
Siemens 3VA1010-4ED32-0AE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-4ED32-0AE0 SENTRON MCCB, 100 A, 3-Pole, 121

MPN3VA1010-4ED32-0AE0

Siemens SENTRON 3VA1010-4ED32-0AE0, 3-pole molded case circuit breaker, 100 A rated continuous current, TM210 thermal-magnetic release, 121 kA breaking capacity at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1010-4ED32-0AE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1010-4ED32-0AE0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA
3VA1010-4ED32-0AE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1010-4ED32-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-4ED32-0AE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts4
3VA1010-4ED32-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-4ED32-0AE0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1010-4ED32-0AE0 is a 3-pole molded case circuit breaker rated for 100 A continuous current at 40 °C ambient, with the TM210 thermal-magnetic release. The thermal derating curve is published: the breaker holds 100 A from 40 °C through 50 °C, then steps down to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. For a panel running at 60 °C ambient — common in sealed enclosures with multiple heat sources — the effective continuous current is 94 A, not the nameplate 100 A. That 6 A difference matters when sizing for a continuous load near the limit.

The 76.2 mm width (3-inch footprint) is standard for 3-pole MCCBs in this class; it fits existing panel cutouts and busbar centers without adapter plates. Front-face protection is IP40, suitable for general-purpose indoor panels where tools are required to access live parts.

Frequently asked questions

Will 3VA1010-4ED32-0AE0 drop into a panel specified around 3VA1010-2ED42-0AE0 without rewiring?

Both are 3-pole SENTRON 3VA frame breakers with the same 76.2 mm width and 130 mm height, so the physical footprint and busbar centers match. The key difference is the release: the -4ED32-0AE0 carries a TM210 thermal-magnetic release (fixed thermal, fixed magnetic), while the -2ED42-0AE0 uses a different release variant. Verify the trip curve and auxiliary contact count against the panel's coordination study before swapping.

MPN
3VA1010-4ED32-0AE0