Skip to main content
Siemens 3VA1010-4ED32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-4ED32-0AC0 MCCB, 100 A, 121 kA at 240 V

MPN3VA1010-4ED32-0AC0

Siemens SENTRON 3VA1010-4ED32-0AC0, Molded case circuit breaker, 3-pole, 100 A, 121 kA at 240 V, TM210 release, 2 auxiliary switches HQ.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1010-4ED32-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1010-4ED32-0AC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA
3VA1010-4ED32-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1010-4ED32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-4ED32-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1010-4ED32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-4ED32-0AC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

MCCB for line protection — 100 A, 121 kA SCCR

The Siemens SENTRON 3VA1010-4ED32-0AC0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 100 A across ambient temperatures from 40 °C through 50 °C before any derating kicks in. At 55 °C it still holds 96 A, and at 70 °C it delivers 90 A — so for most panel environments below 50 °C, the full 100 A rating is available without headroom calculations. The interrupting ratings are the standout here — 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V.

TM210 release and auxiliary contacts

The overcurrent release is the TM210 thermal-magnetic type — fixed thermal pickup, magnetic trip adjustable across the standard range. It ships with 2 auxiliary switches, HQ (high-qualified) contacts rated for control-circuit reliability. This is a line-protection version (not motor-protection), so it's sized for feeder and distribution circuits rather than individual motor starts. The IP40 front protection is standard for panel-mounted breakers — installed in an enclosure, not open-air.

At 76.2 mm wide (roughly 3 inches), 130 mm tall, and 70 mm deep, this breaker fits standard panel-mount cutouts for 100 A frame MCCBs.

Frequently asked questions

Where can I buy 3VA1010-4ED32-0AC0 and get a price?

This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What is the interrupting rating of 3VA1010-4ED32-0AC0 at 240 V?

It interrupts 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V.

Does 3VA1010-4ED32-0AC0 include auxiliary contacts?

Yes — it comes with 2 auxiliary switches, HQ (high-qualified) type, integrated from the factory.

MPN
3VA1010-4ED32-0AC0