Skip to main content
Siemens 3VA1063-2ED36-0BA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1063-2ED36-0BA0 SENTRON MCCB, 63 A, 52.5 kA

MPN3VA1063-2ED36-0BA0

Siemens SENTRON 3VA1063-2ED36-0BA0, 3-pole molded case circuit breaker, 63 A rated continuous current, TM210 thermal-magnetic release, 52.5 kA breaking capacity at 240 V, 70 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1063-2ED36-0BA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1063-2ED36-0BA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1063-2ED36-0BA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1063-2ED36-0BA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1063-2ED36-0BA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1063-2ED36-0BA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1063-2ED36-0BA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

63 A MCCB with TM210 release and undervoltage trip

The Siemens SENTRON 3VA1063-2ED36-0BA0 is a 3-pole molded case circuit breaker rated for 63 A continuous current at 40 °C, with a TM210 thermal-magnetic overcurrent release and an integrated undervoltage release (UVR). Breaking capacity runs 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — so it handles high-fault scenarios across common industrial voltage levels without cascading upstream.

Thermal derating and mechanical endurance

Full 63 A rating holds up to 50 °C ambient; above that it steps down: 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C. That's about a 10 % drop from the nameplate at the top end — factor that into panel thermal budgets.

Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — fits standard SENTRON 3VA panel cutouts and busbar systems. No auxiliary contacts on this variant; the only integrated accessory is the undervoltage release (UVR). The TM210 release is fixed thermal-magnetic — no electronic adjustment, no communication function, no phase-failure detection. It's a straight line-protection breaker for straightforward feeder or distribution duty.

Frequently asked questions

What is the breaking capacity of this MCCB at 415 V?

32 kA at 415 V, with higher ratings at lower voltages (52.5 kA at 240 V) and lower ratings at higher voltages (13.6 kA at 440 V, 7.5 kA at 690 V).

Does the 3VA1063-2ED36-0BA0 include an undervoltage release?

Yes, it comes with an integrated undervoltage release (UVR) as standard — no auxiliary contacts or communication module on this variant.

What is the rated current at elevated ambient temperatures?

Full 63 A up to 50 °C, then derated to 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C.

Where can I buy the 3VA1063-2ED36-0BA0?

Sourced and quoted to order against an RFQ through independent distribution — availability and current pricing confirmed at quote time.

MPN
3VA1063-2ED36-0BA0